Brochure/Catalogue

B
B.112 2028840000
Lightning and surge protection
for control and instrumentation signals
2-stage protection with tension clamp
connection
Slim overvoltage protection terminal with tension clamp
connection
6mm slim fine overvoltage protection
Fast wiring thanks to TS contact and tension clamp
connections
Technical data
Rated voltage (AC) / Rated voltage (DC)
Max. continuous voltage, Uc (AC)
Rated voltage (DC), max.
Operating current, I
max.
Volume resistance
Gas discharge tube
Limiting frequency (-3 dB) at load resistance
Discharge current, max. (8/20 µs)
Lightning test current I
imp
(10/350 µs)
Requirements category acc. to IEC 61643-21
Storage temperature
Ambient temperature (operational)
Protection level
Wire-PE 1kV/µs, typically
Wire-PE 8/20 µs, typically
Wire-wire 1 kV/µs, typically
Wire-wire 8/20 µs, typically
Approvals
Approvals
Dimensions
Height x width x depth mm
Note
Ordering data
Note
Accessories
Note
MCZ OVP HF 5 V 0.3 A
1
2
4
3
OUTIN
5
TS
T1
R1
R2
V2
V4
V1
V5
V11
5 V / 5 V
7 V
10 V
0.3 A
2.50 Ω
Yes
100 MHz (measured in 100-Ω system)
5 kA
D1, C3, C2, C1
-40 °C...85 °C
-40 °C...60 °C
15 V
30 V
15 V
15 V
CE; EAC
91 / 6 / 63.5
Type Qty. Order No.
MCZ OVP HF 5V 0,3A 10 8948620000
End plate
AP MCZ 1,5 SW: 1046410000
MCZ OVP HF 12 V 0.3 A
1
2
4
3
OUTIN
5
TS
T1
R1
R2
V2
V4
V1
V5
V11
13 V / 12 V
13 V
18.5 V
0.3 A
2.50 Ω
Yes
100 MHz (measured in 100-Ω system)
5 kA
C3, D1, C2, C1
-40 °C...85 °C
-40 °C...60 °C
25 V
40 V
25 V
25 V
CE; EAC
91 / 6 / 63.5
Type Qty. Order No.
MCZ OVP HF 12V 0,3A 10 8948610000
End plate
AP MCZ 1,5 SW: 1046410000
MCZ OVP series