Brochure/Catalogue

Discharge capacity
Testing is conducted using voltage and
current pulses according to the
IEC 61643-21 standard concerning
surge protection in networks which
process signals.
Cate-
gory
Testing
pulse
Surge
voltage
Surge
current
Pulse Type
C1 Quick
rising
edge
0.5-2 kV
with
1.2/50 µs
0.25-1 kA
with
8/20 µs
300 Surge
voltage
arrester
C2 Quick
rising
edge
2-10 kV
with
1.2/50 µs
1-5 kA
with
8/20 µs
10 Surge
voltage
arrester
C3 Quick
rising
edge
≥ 1 kV
with
1 kV/µs
10-100 A
with
10/10.000 µs
300 Surge
voltage
arrester
D1 High
power
≥ 1 kV 0.5-2.5 kA
with
10/350 µs
2
Arrester for
lightning
current and
surge voltages
Category C reects the interference
pulses with quick-rising edges and
minimised power. Category D uses
quick-rising edges and high power
to detail the interference pulses. This
energy simulates the high-power
load that stems from coupled partial
lightning currents.
Error mode
The VSSC and VSPC series are tested
pursuant to IEC/EN 61643-21 and
meet Mode 1 and 2 requirements.
More information can be found in
Chapter W.
General technical data
Storage temperature -40 °C…+80 °C
Operating temperature: -40 °C…+70 °C
Air humidity 5%…96% RH with no
condensation
Material: V0, IP 20
Connection: screw connection
screwdriver blade: 0.6 x 3.5 DIN 5264
(for example, 0.6x3.5x200,
order no. 9010110000)
rated torque: 0.5 Nm
max. torque: 0.8 Nm
stripping length: 7 mm
solid: 0.5…4 mm²
exible: 0.5…2.5 mm²
wire-end ferrule with plastic collar:
0.5...2.5 mm²
Remote signalling connection:
screw connection
screwdriver blade: 0.4 x 2.0 DIN 5264
(for example, SD 0.4x2.0x60,
order no. 9037160000)
max. torque: 0.2 Nm
stripping length: 6...6.5 mm
solid: 0.5...1.5 mm²
Dimensions
Height: 90 mm
Height: with remote signalling contact:
98 mm
Depth: 69 mm
Width: 17.8 mm
VARITECTOR SPC
Accessories
Markers
The VSPC BASE lower section can
be labelled with Dekax-5 markers.
The VSPC pluggable modules are
colour coded with Dekax-5 markers
according to their rated voltage.
V-TEST
Testing device for functional tests of
the pluggable VSPC, PU II and PU I
surge protection.
VSPC Ground
This plug is attached to unused wires in
the base element, so that all wires have
the same potential.
B
B.14 2028840000
Lightning and surge protection
for control and instrumentation signals