Brochure/Catalogue

B
B.812028840000
Lightning and surge protection
for control and instrumentation signals
Rated voltage (AC)
Rated voltage (DC)
Max. continuous voltage, Uc (AC)
Max. continuous voltage, Uc (DC)
Rated current I
N
Optical function display
Isolating function
Input attenuation
Pulse-reset capacity
Residual voltage, U
P
typical
Capacitance
Width
Ordering data
Ordering data
Note
12 V
15 V
12 A
No
No
57 V
10.8 nF
7.1
MOV 12 V DC
End plate AP VSSC6 1063110000
Type
Order No.
Qty.
VSSC6 MOV 12VDC
1064530000
8
24 V
34 V
30 V
42 V
12 A
No
No
120 V
4.6 nF
7.1
MOV 24 V UC
End plate AP VSSC6 1063110000
VSSC6 MOV 24VAC/DC
1064540000
8
48 V
60 V
60 V
85 V
12 A
No
No
213 V
2.0 nF
7.1
MOV 48 V UC
End plate AP VSSC6 1063110000
VSSC6 MOV 48VAC/DC
1064570000
8
60 V
85 V
75 V
106 V
12 A
No
No
269 V
1.78 nF
7.1
MOV 60 V UC
End plate AP VSSC6 1063110000
VSSC6 MOV 60VAC/DC
1064600000
8
Rated voltage (AC)
Rated voltage (DC)
Max. continuous voltage, Uc (AC)
Max. continuous voltage, Uc (DC)
Rated current I
N
Optical function display
Isolating function
Input attenuation
Pulse-reset capacity
Residual voltage, U
P
typical
Capacitance
Width
Ordering data
Ordering data
Note
120 V
170 V
150 V
212 V
12 A
No
No
543 V
283 pF
12.2
MOV 120 V UC
End plate AP VSSC6 1063110000
Type
Order No.
Qty.
VSSC6 MOV 120VAC/DC
1064610000
5
240 V
339 V
288 V
407 V
12 A
No
No
1022 V
0.5 nF
12.2
MOV 240 V UC
End plate AP VSSC6 1063110000
VSSC6 MOV 240VAC/DC
1064630000
5
VARITECTOR SSC 6AN
VSSC 6 MOV