User Documentation

4350700000/05/10.14
en
Operating instructions WAVE TTA
Introduction
WAVE TTA is an accurate and stable signal
converter / isolator / alarm generator for use in
measurement and control systems.
Conversion (current to voltage, and vice
versa)
Isolation of temperature sensor and DC
inputs
Linearization of temperature sensor inputs
Transmission of sensor signals over long distance
Characterising signals from DC transmitters
Process alarm generation
Relay control between high and low values
DANGER!
This product may be connected to potentially lethal
voltages!
CAUTION!
Before you remove or mount the unit, turn-off the
power supplies – i.e. to the instrument and to the
relays, if used.
Don’t remove the electronic boards out of the
housing.
Follow ESD installation regulations, including the EMI
precautions given
Package list
The following items are including in the package with the WAVE TTA:
Module WAVE TTA
This Operation instruction guide
Types / article numbers
WAS6 TTA 8939670000 (screw connectors)
WAZ6 TTA 8939680000 (tension clamp c
onnectors)
WAS6 TTA EX 8964310000 (screw connectors)
WAZ6 TTA EX 8964320000 (tension clamp connectors)
CBX100 USB
CBX200 USB
7940025031
8978580000
Interface from PC to WAVE TTA
Interface from PC to WAVE TTA
cULus – Approval for WAVE TTA EX
Class 1, Division 2 / Zone 2 markings (for WAVE TTA EX)
DANGER!
A. This equipment is suitable for use in Class I, Division
2, Groups A, B, C and D hazardous locations or
nonhazardous locations only or the equivalent.
B. EXPLOSION HAZARD – Substitution of components
may impair suitability for use in Class I, Division 2
environments.
C. EXPLOSION HAZARD – The area must be known to
be nonhazardous before servicing/replacing the unit
and before installing or removing I/O wiring.
D. EXPLOSION HAZARD – Do not disconnect
equipment unless po
wer has been disconnected and
the area is known to be non hazardous.
Connections
Power Supply
Analogue Input
Analogue Output
ATEX – Approval for WAVE TTA EX
Approval according ATEX directive EN 60079-0:2012 and for NON Sparking
EN 60079-15:2005: KEMA 09ATEX0136 X
EN 60079-15:2010: WI 14ATEX0001 X
DANGER!
Do not disconnect while circuit is live unless area is
known to be non hazardous.
Devices type WAS6 TTA EX and type WAZ6 TTA EX
shall be installed in an enclosure in type of protection
Ex n or Ex e, providing a degree of protection of at
least IP54. Cable entry devices and blanking elements
shall fulfil the same requirements.
A transient protection device, set at a level not
exceeding 40% of the rated voltage, shall be provided
to prevent the supply voltage (Terminals 24...26) from
being exceeded.
A transient protection device, set at a level not
exceeding 40% of the rated voltage, shall be provided
to prevent the rated voltage of the digital relay outputs
(terminals 34...36 and 44...46) from being exceeded, if
they switch a power supply signal of other apparatus.
•Indicators
Status LED green
Normal status – continuously on
Input open circuit – flashes at 0.5 Hz
Input short circuit – flashes at 5 Hz
Cold Junction error – 2 pulses, rests, 2 pulses
Flash me
mory error – 3 pulses, rests, 3 pulses
Firmware memory error - 4 pulses, rests, 4 pulses
Alarm LEDs red
Status ‘Normal’ – off
Status ‘Alarm’ – on
Status ‘ON delay is active’ – flashes at 0.1 s on, 1.5 s off
Status ‘OFF delay is active’ – flashes at 1.5 s on, 0.1 s off
Configuration
DANGER!
The configuration socket must only be used for
configurating in non-hazardous areas!
The WAVE TTA will be configured with the software TTA-Set and the
interface module CBX100 USB or CBX200 USB. The software
TTA-Set and the user manual are available to download for free on
the Weidmüller website www.weidmueller.com.
Serial Communication
Install and Start Software TTA-Set
Digital Output relais
TP = Testpoint
N/O = Normally Open
N/C = Normally Closed
Specifications
Input types
Thermocouple
Range -200...+1820 °C
Types B, E, J, K , L, N, R, S, T to IEC 60584 plus custom specific
RTD
2, 3, 4 wire, within the range -200...+850 °C, for Pt100, Pt1000 to
IEC 60571 and for Ni100 / Ni1000 to DIN 43760, for Cu 10 and,100
plus custom specic
Potentiometer
10 Ω...100 kΩ
Ex nL IIC: U
o
= 3,5 V; I
o
= 22 mA; P
o
= 20 mW; C
o
= 1 mF; L
o
= 165 mH
Ex nA: U
max
= 3,5 V; I
max
= 22 mA; P
max
= 20 mW
Resistance 10 Ω...5 kΩ
Frequency 2 Hz...100 kHz
Voltage
within the range -200...600 mV (min
span 4 mV),
within the range -20...50 V DC (min span 0.5 V)
Current within the range -20...50 mA (min span 1 mA)
Current Loop supply +24 V DC
Sensor break output Selectable between -2 % and 102 % output
Analogue Output
DC voltage
0...5, 1...5, 0...10, 2...10 V or span-settable between -10...10 V
(min span 2.5 V )
DC current
0...20, 4...20, 0...10 mA, or span-settable between 0...20 mA
(min span 5 mA)
Max load (current /
voltage) 700 Ω / >10 kΩ (>20 kΩ for -10 V…+10 V)
Action Direct or Reverse Acting
Digital Output
Relays 2 x SPCO
Max voltage / current AC 250 V / 2 A
Max voltage / current DC 30 V / 2 A
General Data
Rated voltage
24...240 V AC/DC
24...36 V AC / 24...50 V DC (ATEX Zone 2)
Voltage Limits
18...264 V AC/DC ( VDE)
18…40 V AC / 18…56 V DC (ATEX Zone 2)
Rated power < 3.5 W
Ambient operating range -40...+70 °C
Storage temperature -40...+85 °C
Isolation test 1.5 kVeff 1 min. between PE and Power supply, In- and Output
Isolation test 2.5 kVeff 1 min. between In- and Output
Performance
Accuracy
DC, RTD inputs <0.1% span.
Thermocouple inputs: 0.2% span (or 1 °C) + CJ error
Ambient temp effects
DC & RTD inputs < 0.01%/K
Thermocouple inputs < 0.01% of full scale/K
Step Response/ Cut-off Frequency Settable within 60 ms – 1880 ms / 1 Hz (3 dB)
General Data
Dimensions 92.4 x 112.5 x 45 mm
No. of connections 24
Connection types Screw connection Tension clamp connection
– Clamping range (Rated- / min. / max.) 2.5 / 0.5 / 2.5 mm
2
1.5 / 0.5 / 2.5 mm
2
– Tightening torque 0.4...0.6 Nm 0.4...0.6 Nm
Housing material UL 94 V0
Housing colour Black
Ingress protection IP20
Approvals TTA CE, cULus, GL
Approvals TTA EX CE, cULus Class 1, Div. 2 / Zone 2, ATEX Zone 2
11 12 13 14 15 16
21 22 23 24 25 26
Power supply
11 12 13 14 15 16
21 22 23 24 25 26
In- In+
Voltage Source
11 12 13 14 15 16
21 22 23 24 25 26
Frequency
< 30 V
In- In+
11 12 13 14 15 16
21 22 23 24 25 26
R- R+
RTD 2-wire
11 12 13 14 15 16
21 22 23 24 25 26
In- In+
TC / mV Source
11 12 13 14 15 16
21 22 23 24 25 26
In-
In+
TP-
External Power
Powered mA
Source
Test
mA
TP+
11 12 13 14 15 16
21 22 23 24 25 26
Frequency
< 50 V
In - In+
11 12 13 14 15 16
21 22 23 24 25 26
R- R+
Sense-
RTD 3-wire
11 12 13 14 15 16
21 22 23 24 25 26
Start
Wiper
POT
End
2-wire mA
Sink
11 12 13 14 15 16
21 22 23 24 25 26
+24 V
<
I Return
TP-
Test
mA
TP+
11 12 13 14 15 16
21 22 23 24 25 26
R- R+
RTD 4-wire
Sense-
Sense+
41 42 43 44 45 46
31 32 33 34 35 36
Out + Out-
Output
0…10 V
41 42 43 44 45 46
31 32 33 34 35 36
Output
-10...+10 V
Out- Out+
Output
0...20 mA
41 42 43 44 45 46
31 32 33 34 35 36
Out+ Out-
TP+
Test
mA
TP-
41 42 43 44 45 46
31 32 33 34 35 36
N/C
N/O
COM
Output Alarm 1
41 42 43 44 45 46
31 32 33 34 35 36
N/C
N/O
COM
Output Alarm 2
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
32758 Detmold
Germany
www.weidmueller.com
T II 3 G Ex nA nC [nL] IIC T4
T II 3 G Ex nA nC IIC T4 Gc
Caution! – Potentiometer must be suitable for
non-intrinsicaly safe circuits.
Jack connection
under front flap
CBX100 or CBX200 with
USB connection