Brochure/Catalogue
E
E.172729490000
Temperature transducers
• Isolation and conversion of temperature signals, RTD
(PT100)
• Configuration via DIP switches
• Power supply via the mounting rail bus
• 3-way isolation
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Output voltage
Load impedance current
load impedance voltage
Sensor error detection
General data
Configuration
Voltage supply
Power consumption, max.
Accuracy
Galvanic isolation
Temperature coefficient
Step response time
Ambient temperature
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Pollution degree
Overvoltage category
Approvals
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Note
Accessories
Note
ACT20M-RTI-AO-S
4
3
2
1
5
6
7
8
82 83
IN
Supply
24 V
DC
230 V
AC
PLC
I, U
OUT
Supply
PT100 / 2-/3-/4-wire
PT100 -200…+850 °C
Configurable, min. measurement range 10°C (RTD)
configurable, 0...20 mA, 4...20 mA
configurable, 0(2)...10 V, 0(1)...5 V
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none
DIP switch
24 V DC ± 30 %
0.7 W
absolute accuracy: < ±0.05 % of the measurement range, Basic
accuracy: < ±0.1°C
3-way isolator
≤0.01 % of the measurement range⁄°C or 0.02 °C ⁄ °C
≤ 30 ms
-25 °C...+70 °C
2.5 kV
eff
/1 min.
300 V
eff
IEC 61326-1, NE 21
2
II
cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Type Qty. Order No.
ACT20M-RTI-AO-S 1 1375510000
DIN mounting rail, see accessories
Input
Output
Supply
mA
-
+
V
-
+
+
-
Supply
Electrical connections
Terminal
ACT20M-RTI-AO-S
Input
Power
supply
Output 1
RTD
V mA
2 wire 3 wire 4 wire
1 Sense- Sense-
2 R R- R-
3 R R+ R+
4 Sense+
5 ◼
◼
6 ◻ ◻
7 ◼
8 ◻
◼ = +
◻ = –
Confi guration
Temperature range [°C]
Pt100: -200...+850 °C
Min.
Temp.
S2 Max.
Temp.
S2 Max.
Temp.
S2
1 2 3 4
5 6 7 8 9
10
5 6 7 8 9
10
-200 0 170 ◼
-180 ◼ 5 ◼ 180 ◼ ◼
-150 ◼ 10 ◼ 190 ◼ ◼
-100 ◼ ◼ 15 ◼ ◼ 200 ◼ ◼ ◼
-50 ◼ 20 ◼ 225 ◼ ◼
-25 ◼ ◼ 25 ◼ ◼ 250 ◼ ◼ ◼
-10 ◼ ◼ 30 ◼ ◼ 275 ◼ ◼ ◼
-5 ◼ ◼ ◼ 35 ◼ ◼ ◼ 300 ◼ ◼ ◼ ◼
0 ◼ 40 ◼ 325 ◼ ◼
5 ◼ ◼ 45 ◼ ◼ 350 ◼ ◼ ◼
10 ◼ ◼ 50 ◼ ◼ 375 ◼ ◼ ◼
20 ◼ ◼ ◼ 55 ◼ ◼ ◼ 400 ◼ ◼ ◼ ◼
25 ◼ ◼ 60 ◼ ◼ 450 ◼ ◼ ◼
50 ◼ ◼ ◼ 65 ◼ ◼ ◼ 500 ◼ ◼ ◼ ◼
100 ◼ ◼ ◼ 70 ◼ ◼ ◼ 550 ◼ ◼ ◼ ◼
200 ◼ ◼ ◼ ◼ 75 ◼ ◼ ◼ ◼ 600 ◼ ◼ ◼ ◼ ◼
80 ◼ 650 ◼ ◼
85 ◼ ◼ 700 ◼ ◼ ◼
90 ◼ ◼ 750 ◼ ◼ ◼
95 ◼ ◼ ◼ 800 ◼ ◼ ◼ ◼
100 ◼ ◼ 850 ◼ ◼ ◼
105 ◼ ◼ ◼
110 ◼ ◼ ◼
115 ◼ ◼ ◼ ◼
120 ◼ ◼
125 ◼ ◼ ◼
130 ◼ ◼ ◼
135 ◼ ◼ ◼ ◼
140 ◼ ◼ ◼
145 ◼ ◼ ◼ ◼
150 ◼ ◼ ◼ ◼
160 ◼ ◼ ◼ ◼ ◼
◼ = On
Space-saving signal converters – ACT20M
Temperature transducers