Approval/Certificate/Document of Conformity

[13]
Schedule
[14] EU-TYPE EXAMINATION CERTIFICATE No.
DEMKO 14 ATEX 1338U Rev.5
00-IC-F0056-2 Issue 20.0
This certificate may only be reproduced in its entirety and without any change, schedule included. Page 5 of 6
WQV 4
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 6
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 10
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 16
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 35
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 35N
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 50N
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
TYPE
Rated
voltage
(V)
Rated
Current
(A)
Resistance
across
terminals
(uΩ)
Strip
length
for min
wire
size
(mm)
Solid
wire
size
(mm
2
)
wire size
(mm
2
)
Flexible
wire
size
(mm
2
)
2 wires in
one terminal
(mm
2
)
WQV 70/95
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 70N
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 95/120
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
WQV 120
See
NTI
See NTI
N/A
N/A
N/A
N/A
N/A
**Two alternate constructions under one Cat. No.
NOTE: NTI = Notice to installer
Temperature range
The ambient temperature range is -60°C to +70 °C depending of T-Code.
Refer to [17] Schedule of limitations.
The service temperature range is -60 °C to +110 °C.
Routine tests
According to EN 60079-7 clause 7.1 in combination with clause 6.1 a dielectric strength test has to be carried out. The routine tests may
be performed on a statistical basis according to ISO 2859-1 with an acceptance quality limit (AQL) of 0,04. Routine test is to be carried
out according to Weidmuller procedure “High voltage test” Document -NR: A_10_54.
[16] Descriptive Documents
The scheduled documents are listed in the report no. provided under item no. [ 8 ] on page 1 of this EU-Type Examination Certificate.
[17] Schedule of limitations:
o The feed through and protective conductor terminal blocks are suitable for use in enclosures in atmospheres with flammable
gases and combustible dust. For flammable gases these enclosures must satisfy the requirements according to EN 60079-0 and
EN 60079-7. For combustible dust these enclosures must satisfy the requirements according to EN 60079-31.
o The terminal blocks shall be placed inside a suitable ATEX certified IP54 enclosure for gas atmosphere. For dust atmosphere the
terminal blocks shall be mounted inside a suitable ATEX certified ‘t’ enclosure (EN60079-31).
o The enclosure shall be constructed to block all sun and UV light from affecting the terminal blocks.