Approval/Certificate/Document of Conformity

KEMA ~
(13)
SCHEDULE
(14)
to EC-Type Examination Certificate KEMA 98ATEX1684 U
Installation instructions
Issue No. 2
The Feed Through Terminal Blocks are suitabie for use in enclosures in atmospheres with
flammable gases and combustible dust. For flammable gases these enclosures must satisfy the
requirements according to EN 60079-0 and EN 60079-7. For combustible dust these enclosures
must satisfy the requirements according to EN 50281-1-1.
In combination with other terminal block series and sizes and if other accessories are used the
applicable creepage distances and clearances shall be met.
Regarding the use of end plates, partitions and end brackets the instructions of the manufacturer
must be followed.
If conductors with sm aller cross sections as the rated cross seetion are used, the belanging lower
current has to be laid down in the EC-Type Examination Certificate of the complete equipment.
The Feed Through Terminal Blocks may be used, based on the self-heating when used at the
above mentioned rated current and at ambient temperatures of -50°C to +40 °C at the mounting
position in electrical apparatus, e.g. junction and connection boxes, for temperature class T6. When
the Feed Through Terminal Blocks are used in electrical apparatus of temperature classes T1 up to
T5, the highest temperature of the insulating material shall not exceed the maximum value of the
operating temperature range.
Unused terminals shall be tightened.
Routine test
The routine dielectric strength tests according to EN 60079-7, clause 7.2 or using the method as
laid down in document no. A_10_07 shall be conducted.
(16) Report
KEMA No. 2112447.
(17) Special conditions for safe use
None.
(18) Essential Health and Safety Requirements
Covered by the standards listed at (9).
(19) Test documentation
As Iisted in Test Report No. 2112447.
MEAN-P-Ex61 v2.1