Cross-section No. of conductors Cable ø approx. mm Metric cable glands PG
1.5 mm²
2 8.0 - 11.0 12 16 20 9 11 13.5 16
AWG 16 3 8.7 - 11.0 16 20 25 9 11 13.5 16
4 9.7 - 11.8 16 20 25 9 11 13.5 16
5 10.8 - 13.0 20 25 11 13.5 16
6 10.8 - 14.2 20 25 11 13.5 16
7 10.8 - 14.2 20 25 11 13.5 16
8 13.2 - 16.6 25 32 13.5 16 21
11 13.6 - 16.8 25 32 13.5 16 21
12 17.6 - 16.8 25 32 13.5 16 21
14 14.4 - 17.6 25 32 16 21
16 15.8 - 18.4 25 32 16 21
18 16.6 - 19.2 25 32 21 29
20 17.4 - 20.0 25 32 40 21 29
25 20.2 - 23.0 32 40 21 29
32 23.8 - 24.5 40 29 36
34 22.6 - 25.4 40 29 36
42 25.8 - 29.0 40 50 29 36
50 27.0 - 30.2 40 50 29 36
56 27.8 - 31.0 40 50 29 36
61 28.6 - 31.8 40 50 36
80 33.0 - 36.4 50 63 36 42
90 34.6 - 37.6 50 63 36 42
100 37.8 - 41.4 50 63 42
2.5 mm²
2 9.8 - 12.8 16 20 25 9 11 13.5 16
AWG 12-14 3 10.6 - 13.4 20 25 11 13.5 16
4 11.7 - 14.4 20 25 11 13.5 16
5 13.0 - 16.4 20 25 32 13.5 16 21
6 13.3 - 16.7 25 32 13.5 16 21
7 13.3 - 16.7 25 32 13.5 16 21
8 17.4 - 20.8 25 32 40 21 29
11 18.0 - 20.6 25 32 40 21 29
16 20.6 - 23.4 32 40 21 29
18 21.7 - 24.5 40 29 36
25 26.4 - 29.6 40 50 29 36
34 31.3 - 33.1 40 50 36 42
50 37.0 - 39.4 50 63 42
61 39.0 - 41.5 50 63 42
4 mm²
2 10.7 - 14.1 20 25 11 13.5 16 21
AWG 10-12 4 13.0 - 16.4 25 32 13.5 16 21
5 14.3 - 17.7 25 32 16 21
7 16.2 - 19.6 25 32 21 29 36
11 ca. 24.5 40 29 36
Note:
The values can differ between manufacturers. These gures should be considered as rough guidelines.