User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
Order No
Version: WPD 133 2502850000
Type Order No
WPDPC X33 GY 2503390000
DEK 5/5 MC NE WS 1609801044
Description: Power Feed In Terminal, Busbar
- Type PA6
Phillips-head
Phillips-Combo
Allen-Screw
Torx
Torx-Minus
WPD 133
1100 V
520 A / ΔT 40 K
≤ 40 K / 520 A
0,02mΩ
- Conductor cross section (input = output)
solid stranded
Finely stranded
with wire end
ferrule
Tightening
Torque
rated conductor cross section:
150-300 mm² 150-300 mm² 120-240 mm² 45 Nm
conductor cross section, American Wire Gauge:
300 - 600 kcmil 300 - 600 kcmil 250-500 kcmil 33,9 Nm
Auxiliary connection
rated conductor cross section:
1,5 - 10 mm²
1,5 - 10 mm² 1,5 - 6 mm² 1,2 Nm
conductor cross section, American Wire Gauge:
16 - 8 AWG 16 - 8 AWG 16 - 10 AWG 1,2 Nm
- Contact resistance
with rated conductor, 35 mm²
-60°C…+55°C (for T5 applications)
Insulation material base:
- Ambient temperature range
- Ambient temperature range
-60°C…+40°C (for T6 applications)
-60°C…+55°C (for T4 applications)
- Rated voltage
- Rated current
- Ambient temperature range
- Temperature rise with rated current
* in all colours and optional with hexagon and six lobe drive
slotted head
Modular Terminal Blocks: WPD 133
Accessories:
- Operating temperature range
-60°C…+100°C (insulating material limit)
INSTALLATION INSTRUCTIONS
& CONDITIONS FOR SAFE USE
Modular TERMINAL Blocks: W- Series
CNEX 18 ATEX 0016U
IECEx CNEX 18.0010U
Notified Body No. of Ex - QA: 0344
Label print on package unit: 0344
Standards:
EN 60079-0:2012 + A11 2013 and EN 60079-7:2015
IEC 60079-0: 2011 IEC 60079-7:2015
II 2 GD
Ex eb IIC Gb
Version: WFF 35/AH 6951267 Index: 00 Date: 01.2016
1