Brochure/Catalogue
B
B.114 2737920000
DRI KIT with PUSH IN connection
2 CO contact, AC/DC coil
&LUFXLWGLDJUDP
$&FRLO/('
'&FRLO/('GLRGH
$
$
$
$
Load side
Rated switching voltage / Continuous current 250 V AC / 5 A
Max. switching voltage, AC 250 V
Min. switching power 10 mA @ 24 V, 10 mA @ 12 V, 100 mA @ 5 V
Contact type 2 CO contact with test button (AgSnO)
Mechanical service life 10 x 10
6
switching cycles
Max. switching frequency at rated load 0.1 Hz
General data
Ambient temperature (operational) -40 °C...55 °C
Storage temperature -40 °C...85 °C
Humidity 35...85 % rel. humidity, no condensation
Approvals CE; EAC
Insulation coordinates
Rated voltage 250 V
Impulse withstand voltage 5 kV (1.2/50 µs)
Dielectric strength, Input/Output 5 kV
eff
/ 1min
Dielectric strength of neighbouring contacts 1.5 kV
eff
/1 min.
Dielectric strength to mounting rail
Creepage and clearance distance input – output ≥ 3 mm
Overvoltage category III
Pollution degree 2
Dimensions PUSH IN
Clamping range (nominal / min. / max.) mm² 1.5 / 0.14 / 1.5
Depth x width x height see dimensioned drawing
Note
Further technical data can be found at catalog.weidmueller.com
Electrical endurance
Switching operations
Switching current [A]
10
4
10
5
10
7
10
6
250 V AC inductive load
(cos
φ = 0,4
)
30 V DC inductive load
(L/R = 7 ms)
123
456
0
250 V AC / 30 V DC
resistive load
DC load braking capacity
Resistive Load
Switching voltage [V DC]
Switching current [A]
0.1 51
1020.5
300
200
100
50
40
30
20
0.2
10
Operating voltage range [DC]
2,2
2,0
1,6
1,2
1,0
0,6
0,2
0 +20 +40 +60 +80 +100
Coil voltage [U/Un]
Ambient temperature [°C]
0,4
0,8
1,4
1,8
Operating voltage range [AC]
2,2
2,0
1,6
1,2
1,0
0,6
0,2
0 +20 +40 +60 +80 +100
Coil voltage [U/Un]
Ambient temperature [°C]
0,4
0,8
1,4
1,8
Dimensioned drawing without test button
62.7 mm
58.9 mm
102.1 mm
Dimensioned drawing with test button
62.7 mm
58.9 mm
102.1 mm
Applications
Technical data
• Mounted kit consisting relay, socket and retaining clip
• 100 % function tested
• 100 % check of the dielectric strenght between input - output
• Optional: test button with coloured control voltage marking (AC coil:
red / DC coil: blue)
• Bright status LED (AC coil: red / DC coil: green)
Universal range
D-SERIES – relay modules