Brochure/Catalogue

Digital output
Valve control component for gas group IIC, 35 mA
The ACT20X-SDI-HAO-S solenoid/actuator driver takes a switched input from e.g. a safe area controller and
delivers an corresponding output to operate an actuator in a hazardous area, e.g. Zone 0. It is available in a
single-channel or double-channel version.
EX area Zone 0, 1, 2, 20, 21, 22 Save area Zone 2 /FM Kl. 1 Abt. 2
Channel 1:
Channel 2:
51
52
53
54
Ex-Output Signals
44
43
42
41
14
13
12
11
24
23
22
21
Input signals
Gnd –
Supply +19,2...31,2 V DC
Module status
Module status
42
41
44
43
N.C.
Power Supply
Alarm
Solenoid
V
+
V
+
V
+
V
+
Alarm
Solenoid
Ex label (excerpt)
ATEX FM
U
o
28 V
II 3 G Ex nA nC IIC T4 Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
I
o
100 mA
II (1) G [Ex ia Ga] IIC/IIB/IIA P
o
0.70 mW
II (1) D [Ex iaD] IIC
C
o
= 0.08 µF, L
o
= 2.9 mH
IECEx Example: IIB C
o
= 0.64 µF, L
o
= 12.8 mH
Ex nA nC IIC T4 Gc ATEX version IIA C
o
= 2.1 µF, L
o
= 22.8 mH
[Ex ia Ga] IIC/IIB/IIA Ex Output Terminal (11-14)
[Ex ia Da] IIIC (More details in ATEX certicate)
Application: Inflow control in Ex zone with gas group IIC
&RQWURO
V\VWHP
$&VXSSO\
,JQLWLRQSURWHFWLRQJURXS,,&
$&7;6',+'2
9'&
&KDQQHOGLJLWDOLQSXW
&KDQQHOGLJLWDOLQSXW
$ODUPVLJQDO
9DOYHRSHQ
FORVHGVLJQDO
6ROHQRLGYDOYH
([DODUPVLUHQ
7DQN
=RQH
&KDQQHOGLJLWDORXWSXW
&KDQQHOGLJLWDORXWSXW
(;=RQH
\
%
Output data
For gas group IIC (≤ 35 mA)
Connection terminal
Channel 1 U without load U with load I max
11-12 Min. 24 V Min. 12.5 V 35 mA
11-13 Min. 24 V Min. 13.5 V 35 mA
11-14 Min. 24 V Min. 14.5 V 35 mA
Note
For gas group IIC (≤ 35 mA)
Connection terminal
Channel 2 U without load U with load I max
21-22 Min. 24 V Min. 12.5 V 35 mA
21-23 Min. 24 V Min. 13.5 V 35 mA
21-24 Min. 24 V Min. 14.5 V 35 mA
Note
Removable
terminals
(black)
LED green
= supply
Marker
Removable
terminals
(blue)
LED Channel 2
yellow = active
red = fault
LED Channel 1
yellow = active
red = fault
SIL
SUITABLE
61508
C.16 2729490000
Intrinsically safe signal converters – ACT20X
C