Brochure/Catalogue

D
D.252729490000
Signal converters
Isolation and conversion of DC signals
24 V - sensor supply
Configuration via DIP switch/button
Supply 12-60 V DC
3-way isolation
Technical data
Input
Input voltage
Input current
Input resistance, current
Input resistance, voltage
Sensor supply
Output
Output voltage
Output current
load impedance voltage
Load impedance current
Offset voltage
General data
Galvanic isolation
Linearity
Temperature coefficient
Configuration
Step response time
Voltage supply
Insulation coordination
Standards
EMC standards
Insulation voltage
Impulse withstand voltage
Overvoltage category
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth / Height / Width
Note
Ordering data
Connection type
Screw connection
PUSH IN connection
Note
Accessories
Note
ACT20P-AI-AO-DC
,QSXW




2XWSXWVLJQDOV
&XUUHQW9ROWDJH
&XUUHQW9ROWDJH




/LYH3RVLWLYH
1HXWUDO1HJDWLYH
3RZHU6XSSO\
9
7[
9ROWDJH&XUUHQW
configurable, 0-11 V (min. measurement range 2 V)
configurable, 0-22 mA (min. measurement range 4 mA)
100 Ω
≥ 1
24 V DC
Adjustable, 0...11 V, Output range, min, 2 V
Adjustable, 0...22 mA, Output range, min, 4 mA
> 600 Ω @ 10 V
1 kΩ @ 20 mA
≤ 20 mV
3-way isolator, between input ⁄ output ⁄ supply
< ± 0.1 % of signal range, Typ. ± 0.05 % of signal range
< 0.05 % / °C
DIP switch, Keys and LED display, with reference voltage/current
sources
350 ms
12...60 V DC
IEC 61326-1:2012, UL 61010-1:2012, 3rd Edition
IEC 61326-1
2 kV inputs / outputs
4 kV (1.2/50 µs)
III
Screw connection PUSH IN
1.5 / 0.5 / 2.5
113.7 / 119.2 / 12.5 mm 113.7 / 127.1 / 12.5 mm
Type Qty. Order No.
ACT20P-AI-AO-DC-S 1 1477420000
ACT20P-AI-AO-DC-P 1 2456860000
Universal measurement transducers
Signal converters and monitoring
components – ACT20P