Datasheet

A
A.491460790000 – 2014/2015
connectPower
PRO-E
Technical data
Input
Input voltage
Input current
Input frequency
Input fuse (internal)
Recommended back-up fuse
Output
Output voltage
Output voltage adjustment
Output current
Output power
Residual ripple, breaking spikes
Overload protection
Surge protection
Mains failure bridge-over time
Control at 10...100% load
Parallel connection option
Insulation coordination
Electrical isolation, output-earth
Electrical isolation, input-earth
Electrical isolation, input-output
General data
Ambient temperature (operational)
Storage temperature
Max. perm. air humidity (operational)
Degree of efficiency
Status indicator
Standards
EMC standards
Mounting position, installation notice
Weight
Approvals
Screw connection
Connection cross-section, solid, min. / max.
Depth x width x height
Note
Ordering data
Note
Accessories
Note
CP E SNT 150W 48V 3.3A
²
/
1²
3(
'&
$&
1RWHSRODULW\IRU'&FRQQHFWLRQ
88…132 V AC / 176…264 V AC optional / 250...370 V DC
2 A @ 230 V AC / 3.5 A @ 120 V AC
47...63 Hz
yes / max. 35A
4 A at 230 V AC, characteristic curve C
48 V DC
± 10% nominal output voltage tolerance, adjustable with
potentiometer
3.3 A@48 V DC
150 W
< 100 mV
PP
120~150% Ikonst. of max. output power, automatic restart
55...62 V @ 48 V DC
20 ms
0.5%
Recommended with diode module
0.5 kV
1.5 kV
3 kV
-20°C…70°C (>50°C derating,refer derated curve); 70% rated
load@70°C
-20 °C...+85 °C
5 %…95 % RH
87 % @ 48 V DC
Operation, green LED
EN 60950
EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3
Panel mount, screw fix
820 g
CE
0.34 / 4 mm²
205 / 99 / 40 mm
Type Qty. Order No.
CP E SNT 150W 48V 3.3A 1 1165890000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Switch-mode power supplies
connectPower PRO-E
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com