Data Sheet

Data sheet
OMNIMATE Power - series BU/SU 10.16HP
BUZ 10.16HP/08/180F AG BK BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date May 27, 2019 3:04:48 PM CEST
Catalogue status 23.05.2019 / We reserve the right to make technical changes. 3
Clampable conductor
Cross-section for conductor connection Type
fine-wired
nominal
0.5 mm²
AEH Stripping length nominal
14 mm
Cross-section for conductor connection Type
fine-wired
nominal
1 mm²
AEH Stripping length nominal
15 mm
Cross-section for conductor connection Type
fine-wired
nominal
1.5 mm²
AEH Stripping length nominal
15 mm
Stripping length nominal
12 mm
Cross-section for conductor connection Type
fine-wired
nominal
0.75 mm²
AEH Stripping length nominal
14 mm
Cross-section for conductor connection Type
fine-wired
nominal
2.5 mm²
AEH Stripping length nominal
14 mm
Stripping length nominal
12 mm
Cross-section for conductor connection Type
fine-wired
nominal
4 mm²
AEH Stripping length nominal
12 mm
Stripping length nominal
14 mm
Cross-section for conductor connection Type
fine-wired
nominal
6 mm²
AEH Stripping length nominal
14 mm
Stripping length nominal
12 mm
Cross-section for conductor connection Type
fine-wired
nominal
10 mm²
AEH Stripping length nominal
12 mm
Stripping length nominal
15 mm
Cross-section for conductor connection Type
fine-wired
nominal
16 mm²
AEH Stripping length nominal
12 mm
Stripping length nominal
15 mm
Max. clamping range 16 mm²
Rated data acc. to IEC
tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. no. of poles
(Tu=20°C) 78.3 A
Rated current, max. no. of poles
(Tu=20°C) 67.9 A
Rated current, min. no. of poles
(Tu=40°C) 70.6 A
Rated current, max. no. of poles
(Tu=40°C) 61.3 A
Rated voltage for surge voltage class /
pollution degree II/2 1,000 V
Rated voltage for surge voltage class /
pollution degree III/2 1,000 V
Rated voltage for surge voltage class /
pollution degree III/3 1,000 V
Rated impulse voltage for surge voltage
class/ pollution degree II/2 6 kV
Rated impulse voltage for surge voltage
class/ pollution degree III/2 8 kV
Rated impulse voltage for surge voltage
class/ contamination degree III/3 8 kV
Short-time withstand current resistance
3 x 1s mit 1000 A
Clearance, min. 15.1 mm
Creepage distance, min. 15.1 mm