Data Sheet

Data sheet
OMNIMATE Signal - series LS
LS2HF 3.50/10/90 3.5SN OR BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 1429-0
Fax: +49 5231 14292083
www.weidmueller.com
Technical data
Creation date October 13, 2016 11:49:41 AM CEST
Catalogue status 12.10.2016 / We reserve the right to make technical changes. 3
Rated data acc. to CSA
Rated voltage (Use group B) 150 V
Rated voltage (use group D) 150 V
Rated current (use group B) 12.5 A
Rated current (use group D) 12.5 A
Wire cross-section, AWG, min. AWG 26
Wire cross-section, AWG, max. AWG 16
Rated data acc. to UL 1059
Institute (cURus)
Certificate No. (cURus)
E60693
Rated voltage (use group B) 150 V
Rated voltage (use group D) 150 V
Rated current (use group B) 12.5 A
Rated current (use group D) 12.5 A
Wire cross-section, AWG, min. AWG 26
Wire cross-section, AWG, max.
AWG 16
Reference to approval values Specifications are
maximum values, details -
see approval certificate.
Classifications
ETIM 3.0 EC001284
ETIM 4.0 EC002643
ETIM 5.0 EC002643
ETIM 6.0 EC002643
eClass 6.2 27-26-11-01
eClass 9.1 27-44-04-01
Notes
Notes • Additional colours on request
• Rated current related to rated cross-section & min. No. of poles.
• Wire end ferrule without plastic collar to DIN 46228/1
• Wire end ferrule with plastic collar to DIN 46228/4
• P on drawing = pitch
• Rated data refer only to the component itself. Clearance and creepage distances to other components are to
be designed in accordance with the relevant application standards.
• Crimping shape "A" for wire end ferrules with PZ 6/5 crimping tool are recommended for the largest cable
sizes.
IPC conformity The products are developed, manufactured and delivered according to the internationally recognised IPC-A-610
standard, category "permissible". More extensive demands on the products can be evaluated on request.
Approvals
Approvals