Data Sheet

Data sheet
A-series
AAP22 4 LI-FS 30-70V
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date May 27, 2019 2:03:32 PM CEST
Catalogue status 23.05.2019 / We reserve the right to make technical changes. 3
Conductors for clamping (rated connection)
Blade size 0.6 x 3.5 mm
Clamping range, max. 4 mm²
Clamping range, min.
0.14 mm²
Connection cross-section, stranded,
max. 4 mm²
Connection cross-section, stranded, min. 0.5 mm²
Connection direction top
Gauge to IEC 60947-1 A4
Number of connections 2
Stripping length 12 mm
Twin wire-end ferrules, max. 1.5 mm²
Twin wire-end ferrules, min. 0.5 mm²
Type of connection PUSH IN
Wire connection cross section AWG,
max. AWG 12
Wire connection cross section AWG,
min. AWG 26
Wire connection cross section, finely
stranded, max.
4 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, max. 4 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, min. 0.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max. 4 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min. 0.5 mm²
Wire connection cross-section, finely
stranded, min.
0.5 mm²
Wire connection cross-section, solid
core, max. 4 mm²
Wire connection cross-section, solid
core, min. 0.5 mm²
Rating data
Rated cross-section 4 mm²
Rated voltage 70 V
Rated voltage to adjoining terminal 500 V
Rated current 6.3 A
Current at maximum wires
6.3 A
Standards In accordance with IEC
60947-7-1, In accordance
with IEC 60947-7-3
Volume resistance according to IEC
60947-7-x 1 mΩ
Power loss in accordance with IEC
60947-7-x 0.04 W
Rated impulse withstand voltage 4 kV
Pollution severity
2
Surge voltage category III
UL rating data
Certificate No. (cURus)
E60693
Conductor size Factory wiring max.
(cURus) 10 AWG
Conductor size Factory wiring min.
(cURus) 26 AWG
Conductor size Field wiring max. (cURus)
10 AWG
Conductor size Field wiring min. (cURus) 26 AWG
Current size B (cURus) 10 A
Current size D (cURus) 10 A
Voltage size B (cURus)
300 V
Voltage size D (cURus) 300 V
Classifications
ETIM 6.0 EC000899
eClass 6.2 27-14-11-25
eClass 9.0 27-14-11-16
eClass 9.1 27-14-11-16
Approvals
Approvals
ROHS Conform