Datasheet

Terminals, W-Series
D.76
D
Accessories – Electrical distribution
WQV screw cross-connector
When used together with W-series termi-
nals, WQV insulated cross-connection
units guarantee absolute safety for finger
and back-hand in accordance with the
accident prevention regulation “Electrical
systems and equipment” (VGB4).
It is very easy to produce individual config-
urations thanks to the many different op-
tions offered by the WQV cross-connec-
tion system, by breaking out individual
segments, creating any required number
of poles or routing two potentials in paral-
lel, etc.
Technical instructions
The full rated current of the terminals
can be routed across any number of
poles.
No end plates or partition plates needed
for adjacent WQV up to 400 V.
Assembly
Place the WQV in the cross-connection
channel in the middle of the terminal
and screw tight.
Individual WQV segments can be bro-
ken out by bending over or using the
WAW1 tool. It is then possible to bridge
individual or several terminals.
Captive fixing screws.
Snap onto the clamped support – sim-
ple overhead assembly.
Any number of poles (extending)
Pre-fitted cross-connectors can be set
one after the other to produce any re-
quired number of poles.
To do so, arrange the last and first contact
points of two identical WQVs so that they
overlap.
First, remove the fixing screw and
screwdriver guide (insulated part) at one
of the outer contact points of one of the
WQVs.
Then insert the WQV without fixing
screw and insulated part. At the same
time, insert an unmodified WQV in par-
allel so as to produce an overlap at the
connection. The connection is screwed
tight using the fixing screw of the un-
modified WQV.
Routing 2 potentials in parallel
In spite of only having 1 channel, the
WQV cross-connection system can still
be used for offset cross-connections.
See the photo “parallel skipping”.
WQV in combination
with a socket contact and test plug
Remove the fixing screw and insulation
part of the WQV.
Screw the socket in at this point. This
now makes it possible to integrate a
safe test point.