User guide

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
32
1066540000/01/12.11
51
52
53
54
Input signals
44
43
42
41
14
13
12
11
24
23
22
21
+
Current
RT D
TC
Connection, wires
+
Current
RT D
TC
Connection, wires
Output signals
Supply and module status
Supply -
Supply +19.2...31.2 VDC
N.C.
Module status
Module status
mA
mA
4...20 mA
+
-
42
41
44
43
-
+
-
-
mA
mA
4...20 mA
Analogue, 0/4...20 mA
2-wire supply +
2-wire supply -
2-wire supply +
2-wire supply -
Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G
Zone 2 / FM Cl. 1,
div. 2, gr. A-D or safe area
Channel 1
Channel 1
Channel 2
Channel 2
Illustration 7-6: Applications
RTD Input
Pt100, according to -200…+850 °C, IEC 60751
Ni100, according to -60…+250 °C, DIN 43760
Sensor types
(* = without short circuit detection)
Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.) 50
Sensor current nom. 0.2 mA
Effect of sensor cable resistance (3/4-wire) < 0.002
Sensor error detection (programmable) ON/OFF