User guide

Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)
1066540000/01/12.11
55
7.5.2 Status/Alarm LEDs
51
CH2
41
54
44
21 22
23
24
ACT20X
PWR
11 12
13
14
CH1
LED 1
LED 2
LED 3
Illustration 7-15: Status/Alarm LEDs
Channel 1 Channel 2
Condition LED 1
LED 2 Output LED 3 Output
Status
Relay (NC)
Device OK
activated OFF active energized
defective red inactive de-energized
signal limit
exceeded
red
flashing
inactive de-energized
Channel 1
fixed loop break
limit exceeded
green
flashing
red
blinking
inactive de-energized
activated OFF active energized
defective red inactive de-energized
signal limit
exceeded
red
flashing
inactive de-energized
Channel 2
fixed loop break
limit exceeded
green
flashing
red
blinking
inactive de-energized
No supply OFF OFF OFF OFF OFF de-energized
Device failure OFF red OFF red OFF de-energized
Blinking: 50% ON and 50% OFF __|¯¯¯¯|____|¯¯¯¯|____|¯¯¯¯|____
Flashing: 8% ON and 92% OFF __|¯|_______|¯|_______|¯|_______
Table 7-9: Status/Alarm LEDs