7.5.3 Electrical Connections
Terminal Function Connector Terminal Function Connector
11 I Passive 41 Out
12 I Passive + 42 Out +
output
channel 1
13 I Active Return 43 Out
14 I Active Supply
Ex input
channel 1
44 Out +
output
channel 2
21 I Passive 51 GND
22 I Passive + 52 +24 V DC
power supply
23 I Active Return 53 NC
24 I Active Supply
Ex input
channel 2
54 COM
status relay
Table 7-10: Electrical Connections
7.5.4 Specifications
Features
HART-compatible for 0.5...2.5 kHz
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The active or passive mA current signal inputs are completely electrically isolated.
The device detects automatically whether an active or passive current signal is connected.
The two-channel device can be used as a signal splitter.
Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
Front LEDs indicates operation status and malfunction.
3-way galvanic isolation between input, output and power supply.