WAVESERIES Thermo Signal Conditioners for Current and Voltage Output Type Screw-type connection WTS4 Thermo Select Cat. No. 8432300000 Tension clamp connection WTS4 Thermo Select 8432310000 Read these instructions before using the product and retain for future information.
1 General instructions The WAVESERIES Thermo signal conditioner should only be installed by qualified staff. The Thermo signal conditioner should only be powered up following professional installation. 2 Application WAVESERIES Thermo signal conditioners can be used to connect to the following thermocouple types: K, J, T, E, N, R, S and B. The temperature range and the type of thermocouple can be set by the DIP switches on the printed circuit board.
Mounting and dismounting Warning!! Mounting and dismounting may only be carried out when the power supply has be disconnected. Failure to observe will lead to considerable damage! 3.1 Mounting onto TS 35 DIN rails (s. Fig. 1) 3.2 Pluggable electronic components for range alteration (depending on model) (s. Fig. 2) 1. Remove connector, (depending on model either screw-type or tension clamp). 2. Press locking clips on both sides of the enclosure. 3. Pull out the circuit board.
3.3 Pluggable cross-connections for voltage supply (s. Fig. 3) A maximum feed through of 2 A is possible. If a signal conditioner is accidently rotated through 180°, the cross-connection cannot be inserted. 3.4 Labelling possibilities (s. Fig. 4) WS 10 connector markers can be used to label module. 4 Calibration Warning!! The power supply must be disconnected, before changing the signal conditioner settings using the DIP switches.
4.1 Setting the DIP switches Warning!! The Thermo signal conditioner must be protected against a direct electrostatic discharge when setting the DIP switches.
Selecting the min.
Selecting the temperature span Span 100 °C 150 °C 200 °C 250 °C 300 °C 350 °C 400 °C 450 °C 500 °C 550 °C 600 °C 650 °C 700 °C 750 °C 800 °C 850 °C 900 °C 950 °C 1000 °C DIP switch 2 1 2 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON OFF ON OFF ON 3 ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON 4 ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF 5 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
1050 °C 1100 °C 1150 °C 1200 °C 1250 °C 1300 °C 1350 °C 1400 °C 1450 °C 1500 °C 1600 °C 1700 °C 1800 °C OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Warning!! Should a temperature range be selected, that is above the maximum possible range, then the module sets itself to the greatest possible range.
Output 0 ... 10 V 0 ... 20 mA 4 ... 20 mA DIP switch 2 6 7 ON OFF OFF OFF OFF ON Filter OFF ON DIP switch 2 8 OFF ON 5 Electrical connection (s. Fig. 5) 6 Dimensions (s. Fig.
7 Notes on CE labelling of WAVESERIES modules WAVESERIES modules, that carry CE-labelling, fulfil the requirements of the EU-Guidelines 89/336/EU “electromagnetic compatibility” and the therein listed harmonised European Norms (EN). The declarations of conformity are, in accordance with the abovementioned EU-Guideline, Article 10, held at the following address for the relevant authorities: Weidmüller Interface GmbH & Co.
Accuracy (at 23 °C ambient temperature) Type K -200 ... -150 °C -150 ... 1200 °C 1200 ... 1372 °C Type J -200 ... -150 °C -150 ... 1200 °C Type T -200 ... -150 °C -150 ... 400 °C Type E -200 ... -150 °C -150 ... 1000 °C Type N -200 ... -150 °C -150 ... 1300 °C Type R -50 ... 200 °C -200 ... 1760 °C Type S -50 ... 200 °C 200 ... 1760 °C Type B 50 ... 250 °C 250 ... 500 °C 500 ... 1820 °C ±5 K +0.1 K from span ±3 K +0.1 K from span ±4 K +0.1 K from span ±4 K +0.1 K from span ±3 K +0.1 K from span ±5 K +0.
Step response time - with active filter function: Open-circuit recognition max. 1.1 s max. 6 s output signal > 10 V or > 20 mA, LED blinking Sensor current for open-circuit recognition typ. 0.25 µA Output Output signal Turning on the filter function Output offset voltage Load resistance Output offset current Load resistance adjustable using DIP switches adjustable using DIP switches max. 0.05 V ≥ 1 kΩ max.
EMC specification General Current consumption - by current output according to EN 55011, class B, group 1 according to EN 50081-1 according to EN 50082-2 Voltage supply Cross-connection, upper Cross-connection, lower Operating temperature Storage temperature 28 mA ... 33 mA ... 38 mA Iout = 20 mA 18 mA ... 23 mA ... 28 mA Uout = 10 V 19.2 Vdc ... 24 Vdc ... 28.8 Vdc 24 V, max. 2 A 0 V, max. 2 A 0 ... +55 °C -20 ...
9 Accessories Cross-connection ZQV 2,5N/2 black Cross-connection ZQV 2,5N/2 red Cross-connection ZQV 2,5N/2 blue Cross-connection ZQV 2,5N/2 yellow 1718080000 1717900000 1717990000 1693800000 Terminal connector, 2-pole for screw-type connection BLZ 5,08/2 - orange 1526460000 - black 1526410000 Terminal connector, 2-pole for tension clamp connection BLZ 5,08/2 - orange 1707460000 - black 1707700000 Connector markers WS 10/5 Multicard for plotter labelling WS 10/5 blank 1635010000 1060860000 In the intere