Beipackinformation Operating instructions Notice d’utilisation 1 11 21 Analogsignaltrenner WAVEANALOG DC/Alarm aus der WAVESERIES Analog signal isolators WAVEANALOG DC/Alarm from the WAVESERIES Séparateur analogique de signal WAVEANALOG DC/Alarm de la gamme WAVESERIES R.T.Nr. 4288810000/08.
Analog signal isolators WAVEANALOG DC/Alarm from the WAVESERIES Type Screw connection WAS5 DC/Alarm Tension clamp connection WAZ5 DC/Alarm Cat. No. 8543820000 8543880000 Please read these instructions before using the product and retain for future information.
1. General instructions Warning! The analogue signal isolators of the WAVEANALOG DC/Alarm may only be installed by qualified personnel. Be sure not to connect the unit to power supply before appropriate installation. Do not select ranges during operation, because live parts are exposed during this process. Only use a screwdriver which is properly insulated against the voltage applied to the input when fine adjusting the potentiometers on the front.
3. Configuration 3.1 Equipment A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals. 3.2 Opening the unit Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on both sides (1). Pull out the top part of the housing and the electronics section until they lock (2). 2 1 1 3.3 Settings Low trip, high trip, FAILSAFE or NON FAILSAFE are set via the DIP switch. SW1 in accordance with the following tables.
Selecting the operating mode SW 1 Function Channel A High Trip Channel A Low Trip Channel B High Trip Channel B Low Trip FAILSAFE, Channel 1& 2 NON FAILSAFE, Channel 1& 2 NON FAILSAFE: FAILSAFE: Low trip: High trip: Signal threshold: Hysteresis: 14 1 1 0 2 3 4 0 1 0 1 1 0 The relay picks up when the alarm is triggered. The relay drops out when the alarm is triggered. An alarm is also triggered in the FAILSAFE mode, if, for example, the operating voltage to the module fails.
3.4.
3.5.
4. Mounting Die The analogue signal isolators are mounted on standard TS 35 rails. 5. Electrical connection Terminal assignments 1 Current input max. 20 mA 2 Voltage input max. 10 V 3 Input GND 4 Supply voltage + 24 Vdc (cross-connected) 5 Supply voltage 0V (cross-connected) 6 Supply voltage 0V (cross-connected) 7 Relay A contakt 11 8 Relay A contakt 12 9 Relay A contakt 14 10 Relay B contakt 21 11 Relay B contakt 22 12 Relay B contakt 24 Wire cross-section max. 2.
6. Dimensions in mm GND 73.4 Cross-connections for power supply 111.4 38 92.4 24 Vdc 17.
7. Accessories (cross-connection) Designation ZQV 2,5 N/2 yellow ZQV 2,5 N/2 red ZQV 2,5 N/2 blue ZQV 2,5 N/2 black Cat. No. 1693800000 1717900000 1717990000 1718080000 Connection markers Designation WS 10/5 Multicard for plotter marking WS 10/5 Neutral Cat. No. 1635010000 1060860000 8.