Beipackinformation Operating instructions Notice d’utilisation 1 9 17 Analogsignaltrenner WAVEANALOG PRO Bridge aus der WAVESERIES Analog signal isolators WAVEANALOG PRO Bridge from the WAVESERIES Séparateur analogique de signal WAVEANALOG PRO Bridge de la gamme WAVESERIES R.T.Nr. 4288820000/03.
Analog signal isolators WAVEANALOG PRO Bridge from the WAVESERIES Type Screw connection WAS4 PRO Bridge Tension clamp connection WAZ4 PRO Bridge Cat. No. 8581200000 8581210000 Please read these instructions before using the product and retain for future information.
1. General instructions Warning! The analogue signal isolators of the WAVEANALOG PRO may only be installed by qualified personnel. Be sure not to connect the unit to power supply before appropriate installation. Do not select ranges during operation, because live parts are exposed during this process. Only use a screwdriver which is properly insulated against the voltage applied to the input when fine adjusting the potentiometers on the front.
3. Configuration 3.1 Equipment A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals. 3.2 Opening the unit Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on both sides (1). Pull out the top part of the housing and the electronics section until they lock (2). 2 1 1 3.
Input voltage 0...10 mV 0...20 mV 0...50 mV 0...100 mV 0...200 mV 0...500 mV -10 mV...10 mV -20 mV...20 mV -50 mV...50 mV -100 mV...100 mV -200 mV...200 mV -500 mV...500 mV Output 0...+10 V 0...+ 5 V 0...20 mA 4...20 mA Supply voltage to the bridge +10 V +5V +4,8...+10,2 V adjustable +4,8...
3.4 Application 230 Vac ~ 24 Vdc Power supply + 10 11 12 7 Bridge R4 - PLC 9 0...
4. Mounting Die The analogue signal isolators are mounted on standard TS 35 rails. 5. Electrical connection Terminal assignments 1 Supply voltage to the bridge + 2 Supply voltage to the bridge 3 Not assigned 4 Input + 5 Input 6 Not assigned 7 Output 0/4...20 mA 8 Output 0...5/10 V 9 Output 0 V- reference potential 10 Power supply + 24 Vdc (cross-connected) 11 Power supply - GND (cross-connected) 12 Not assigned Wire cross-section max. 2.5 mm2 Multi-wire conncection max.
Dimensions in mm GND 73.4 Cross-connections for power supply 111.4 38 92.4 24 Vdc 90 17.5 6.
7. Accessories (cross-connection) Designation ZQV 2,5 N/2 yellow ZQV 2,5 N/2 red ZQV 2,5 N/2 blue ZQV 2,5 N/2 black Cat. No. 1693800000 1717900000 1717990000 1718080000 Connection markers Designation WS 10/5 Multicard for plotter marking WS 10/5 Neutral Cat. No. 1635010000 1060860000 8. Notes on CE marking The WAS5/WAZ5 PRO Freq.