Beipackinformation 1 Operating Instructions 15 Notice d’utilisation 27 Analogsignaltrenner WAVEANALOG PRO RTD aus der WAVESERIES RT Nr.
Analogue Signal Isolators WAVESERIES WAVEANALOGUE PRO RTD MODEL Screw terminal connection WAS5 PRO RTD Tension clamp connection WAZ5 PRO RTD Order Number 8560700000 8560710000 Please read these instructions before using the product and retain for future information.
1. General instructions Warning! The analogue signal isolators of the WAVEANALOGUE PRO series may only be installed by qualified personnel. Be sure not to connect the unit to power supply before appropriate installation. Do not select ranges during operation, because live parts are exposed during this process. Only use a screwdriver which is properly insulated against the voltage applied to the input when fine adjusting the potentiometers on the front.
3. Configuration 3.1 Equipment A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals. 2 3.2 Opening the unit Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on 1 both sides (1). Pull out the top part of the housing and the electronics section until they lock (2). 3.
Selecting the inputs Input PT100 2-wire PT100 3-wire PT100 4-wire R 2-wire NI100 2-wire NI100 3-wire NI100 4-wire Potentiometer SW1 2 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 3 1 1 1 1 0 0 0 0 Selecting the minimum input value SW1 min 0º C –10º C –20º C –25º C –30º C –40º C –50º C –60º C –70º C –80º C –90º C 18 Rmin 0Ω 10 Ω 20 Ω 25 Ω 30 Ω 40 Ω 50 Ω 60 Ω 70 Ω 80 Ω 90 Ω Potimin 0% 10% 20% 25% 30% 40% 50% 60% 70% 80% 4 1 1 1 1 1 1 1 1 0 0 0 5 1 1 1 1 0 0 0 0 1 1 1 6 1 1 0 0 1 1 0 0 1 1 0 7 1 0 1 0 1 0 1
SW1 min –100º C –150 °C –200 °C Rmin 100 Ω 150 Ω 200 Ω Special range Potimin 4 0 0 0 0 5 1 0 0 0 6 0 1 1 0 7 0 1 0 0 Activating the manual fine adjustment manual calibration off on SW1 8 0 1 1 = on 0 = off 19
Selecting the measuring range T 40K 50K 60K 70K 80K 90K 100K 110K 120K 125K 130K 140K 150K 160K 170K 180K 190K 200K 250K 300K 350K 400K 450K 500K 550K 20 R 20 Ω 25 Ω 30 Ω 35 Ω 40 Ω 45 Ω 50 Ω 55 Ω 60 Ω 62,5 Ω 65 Ω 70 Ω 75 Ω 80 Ω 85 Ω 90 Ω 95 Ω 100 Ω 125 Ω 150 Ω 175 Ω 200 Ω 225 Ω 250 Ω 275 Ω Poti 20% 25% 30% 35% 40% 45% 50% 55% 60% 62,5% 65% 70% 75% 80% 85% 90% 95% 100% – – – – – – – 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 2 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 SW2 3 1 1 1 1 0 0
T 550K 600K 650 K 700K 750K 800K 850K 900K R 275 Ω 300 Ω 325 Ω 350 Ω 375 Ω 400 Ω 425 Ω 450 Ω Poti – – – – – – – – 1 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 SW2 3 1 1 1 1 0 0 0 0 4 1 1 0 0 1 1 0 0 5 1 0 1 0 1 0 1 0 Selecting the output SW2 Output 0…10 V 0…20 mA 4…20 mA 6 1 0 0 7 0 0 1 1 = on 0 = off 21
Selecting the step response time SW2 8 1 0 Step response slow fast 1 = on 0 = off 3.4 Terminal assignment of the sensors Terminal assignment for 2-, 3-, 4-wires and potentiometers.
4. Mounting The analogue signal isolators are mounted on standard TS 35 rails. Electrical connection Terminal assignments 10 11 12 2 max. 2,5 mm Anschlußquerschnitt Wire cross-section max. 2.5 mm2 2 Mehrleiteranschluß max. 1 mm Multi-wire conncection max. 1 mm (zwei same Leitercross-section) gleichen Querschnitts) (two wires with 2 We i dm ü l le r 8 nc 7 9 0V 24V V 0...10V V/I nc 8560700000 3 RTD Sense 4 nc 1 RTD 2 Sense 06 PS cc I cc 0/4...20mA 12 11 WAS5 PRO RTD 10 V.
6.
7. Accessories (cross-connection) Designation ZQV 2,5 N/2 yellow ZQV 2,5 N/2 red ZQV 2,5 N/2 blue ZQV 2,5 N/2 black Cat. No. 169380 171790 171799 171808 Connection markers Designation WS 10/5 Multicard for plotter marking WS 10/5 Neutral Cat. No. 163501 106086 8. Notes on CE marking The WAS5/WAZ5 RTD analog signal isolators are marked CE in accordance with the EU directives 89/336/EEC "Electromagnetic Compatibility" and 73/23/EEC (low-voltage directive) detailing the Harmonized European Standards (EN).
Weidmüller Interface GmbH & Co. Postfach 30 30 D-32720 Detmold Tel.