Beipackinformation Operating instructions Notice d’utilisation 1 9 17 WAVECONTROL VMA Vac Spannungsüberwachungsmodul WAVECONTROL VMA Vac Voltage - monitoring module WAVECONTROL VMA Vac Module de contrôle de tension R.T.Nr. 4288400000/03.
WAVECONTROL VMA Vac Voltage - monitoring module Type Screw connection WAS2 VMA Vac Tension clamp connection WAZ2 VMA Vac Cat. No. 8581220000 8581230000 Please read these instructions before using the product and retain for future information.
1. General instructions Warning! Voltage-monitoring modules from the WAVECONTROL range should only be installed by qualified staff. Be sure not to connect the unit to power supply before appropriate installation. Do not select ranges during operation, because live parts are exposed during this process. Be sure to observe the national regulations for installation and selection of cables.
3. Configuration 3.1 Equipment A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals. 3.2 Opening the unit Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on both sides (1). Pull out the top part of the housing and the electronics section until they lock (2). 3.3 Settings The input voltage and the output signals are selected in accordance with the following tables.
Selecting the input Input 0...30 Vac 0...70 Vac 0...130 Vac 0...250 Vac 0...450 Vac Wiring diagram 0V Vac 1 2 1 3 1 4 1 5 1 6 Selecting the output Output 0...10 V 0...20 mA 4...20 mA Wiring diagram GND 1 U/I 9 7 9 8 9 8 Switching the current output Output 0...20 mA 4...
3.4 Application 230 Vac ~ 24 Vdc PLC 7 9 WAVE CONTROL VMA Vac 8581220000/85811230000 L1 L2 L3 8 M 3~ U 1 2 3 4 5 6 0 20 mA 10 11 12 4. Mounting The analogue signal isolators are mounted on standard TS 35 rails.
5. Electrical connection Terminal assignments 1 Input OV - reference potential 2 30 Vac 3 70 Vac 4 130 Vac 5 250 Vac 6 450 Vac 7 Voltage output 0...10 V 8 Current output 0/4...20mA 9 Output O V- reference potential GND 1 10 Power supply + 24 Vdc (cross-connected) 11 Power supply OV GND 2 (cross-connected) 12 not assigned Wire cross-section max. 2.5 mm2 10 11 12 7 8 9 1 2 3 4 5 6 Multi-wire conncection max.
Dimensions in mm GND 73.4 Cross-connections for power supply 111.4 38 92.4 24 Vdc 90 22.5 6.
7. Accessories (cross-connection) Designation ZQV 2,5 N/2 yellow ZQV 2,5 N/2 red ZQV 2,5 N/2 blue ZQV 2,5 N/2 black Cat. No. 1693800000 1717900000 1717990000 1718080000 Connection markers Designation WS 10/5 Multicard for plotter marking WS 10/5 Neutral Cat. No. 1635010000 1060860000 8. Notes on CE marking The WAS5/WAZ5 PRO Freq.