User Manual
WI-I/O 9-L-x Installation Guide
WI-I/O 9-L-x v1.6 Page 36 of 39
This section details the specifications for each unit.
Input/output Number Additional information
Digital inputs 2
Dry-contact digital inputs slow-pulsed at 10Hz.
All inputs are suitable for voltage free contacts (e.g. mechanical
switches) or NPN transistor devices (e.g. electronic proximity
switches).
NOTE: PNP transistor device inputs are NOT suitable.
Status outputs 2 Separate System OK and Setpoint Status
Analog inputs 1
0-20mA differential input; 16-bit resolution, 0.1% accuracy, 10 ohm
input impedance.
Thermocouple inputs 1
J, K or T type thermocouple with on-board cold-junction
compensation.
Cold junction compensation accuracy ±1º over ambient temp
range: -40º to +70ºC.
Power supply 1
9-30 VDC 1 Amp CSA certified Class 2 power supply. For use in
Class 1 Div 2 explosive areas, the power supply must be approved
for Class 1 Div 2 use.
WARNING: Explosion hazard - do not disconnect while circuit is
live unless area is known to be non-hazardous.
Transmitter 1
1-Watt Frequency Hopping Spread Spectrum (FHSS) Transmitter.
Frequency 902-928 MHz
Actual frequency range depends on country.
Input/output Number Additional information
Digital outputs 3 Voltage-free contacts rated at 250 VAC, 1A, 30VDC 1A
2 for digital inputs and 1 for setpoint.
Status outputs 2 Separate System OK and communication failure output.
Analog output 1 16-bit resolution, 0.1% accuracy, single-ended source output.
Power supply 1 9-30 VDC 1 Amp CSA certified Class 2 power supply. For use in
Class 1 Div 2 explosive areas, the power supply must be
approved for Class 1 Div 2 use.
WARNING: Explosion hazard - do not disconnect while circuit is
live unless area is known to be non-hazardous.
Radio receiver 1 High sensitivity FHSS UHF radio receiver.
Frequency 902 – 928 MHz Actual frequency range depends on country.
Sensitivity -110 dBm At PER 8%.