Install Instructions

Boiler
Model
Number
0–2,000
feet altitude
2,000–4,500
feet altitude
(Canada)
Net AHRI Ratings
Chimney
Size
Boiler Water
Content
(Gallons)
Input
(Btuh)
DOE Heating
Capacity
(Output) (Btuh)
Input
(Btuh)
(Output)
(Btuh)
Sq. Ft.
Steam
Steam
Btuh
Water
Btuh
Water Steam
(to Waterline)
(Note 1 & 2) (Note 3) (Note 4) (Note 5)
*EG-30- 75,000 62,000 67,500 56,000 196 47,000 55,000 5"I.D. x 20' 12.3 8.4
*EG-35- 100,000 83,000 90,000 75,000 258 62,000 73,000 5"I.D. x 20' 12.3 8.4
*EG-40- 125,000 104,000 112,500 93,000 325 78,000 91,000 6"I.D. x 20' 14.8 9.8
*EG-45- 150,000 125,000 135,000 112,000 392 94,000 110,000 6"I.D. x 20' 14.8 9.8
*EG-50- 175,000 145,000 157,500 131,000 454 109,000 128,000 7"I.D. x 20' 17.3 11.2
*EG-55- 200,000 167,000 180,000 150,000 521 125,000 146,000 7"I.D. x 20' 17.3 11.2
*EG-65- 250,000 209,000 225,000 188,000 654 157,000 183,000 8"I.D. x 20' 19.8 12.6
*EG-75- 299,000 247,000 270,000 216,000 770 185,000 217,000 8"I.D. x 20' 22.3 14.0
EGH-85- 349,000 280,000 315,000 252,000 875 210,000 243,000 9"I.D. x 20' 24.8 15.4
EGH-95- 400,000 320,000 360,000 288,000 1,000 240,000 278,000 10"I.D. x 20' 27.3 16.8
EGH-105- 450,000 360,000 - - 1,125 270,000 313,000 10"I.D. x 20' 29.8 18.2
EGH-115- 500,000 400,000 - - 1,250 300,000 348,000 12"I.D. x 20' 32.3 19.6
EGH-125- 550,000 440,000 - - 1,375 330,000 383,000 12"I.D. x 20' 34.8 21.0
Boiler
Model
Number
DOE season efciency (AFUE)
Water Steam
SPDN SPDL PIDN SPDN SPDL PIDN
EG-30
PEG-30
82.2 84.2 84.3 81.0 82.9 83.0
EG-35
PEG-35
82.0 83.7 83.6 81.3 82.5 82.9
EG-40
PEG-40
82.5 84.3 84.0 81.5 83.2 82.9
EG-45
PEG-45
82.4 84.0 83.5 81.6 83.0 82.9
EG-50
PEG-50
82.9 84.4 83.8 81.9 83.7 82.8
EG-55
PEG-55
82.5 84.2 83.8 81.9 83.5 82.8
EG-65
PEG-65
82.6 84.0 84.0 82.0 82.8 83.0
EG-75
–– –– 82.7 –– –– 82.4
Part Number 550-110-639/0512
38
EG
PEG
EGH Gas-firEd boilErssEriEs 4 — boilEr manual
Notes (Table 16)
* Add prefix “P” for package boiler completely assembled and
wired with jacket and controls (PEG-30-S through PEG-65-S
only).
1.
EG-30 thru 75:Addsufx“SPD”or“SP”forstandingpilot;
add “PID” or “PI” for electronic ignition (30-65 — damper
requiredinU.S.;optionalinCanada);add“N”fornatural;add
“Lforpropane;add“W”forwater;add“S”forsteam;add“T
fortanklessheater;add“P”forprovisionaltanklessheater.
EGH-85 & 95:Addsufx“SP”forstandingpilot;add“PI”for
electronicignition (damper available on PI only);add“N”
fornatural;add“Lforpropane;add“W”forwater;add“S
forsteam;add“T”fortanklessheater(tanklessavailableon
EGH-85thru125 PIWaterandSteam;EGH-85 and95SP
Steamonly);add“P”forprovisionaltanklessheater.
EGH-105 thru 125: Add suffix “PI” for electronic ignition
(damperavailableonPIonly);add“W”forwater;add“Sfor
steam;add“T”fortanklessheater.
2. EGH water boilers tested for 50 P.S.I working pressure.
3. Based on standard test procedures prescribed by the United
States Department of Energy.
EG-75 thru EGH-125: CSA Gross output.
4. EGH-105 thru 125 may be installed at altitudes of 2,000-4,500
feet subject to acceptance by Provincial Inspections Authority
based on field tests of individual installations.
5. Net AHRI ratings are based on net installed radiation of
sufficient quantity for the requirements of the building and
nothing need be added for normal piping and pick-up. Water
ratingsarebasedonapipingandpick-upallowanceof1.15;
steam ratings on an allowance of 1.333. An additional allow-
ance should be made for unusual piping and pick-up loads.
Consult local Weil-McLain representative.