SERIES 4 — GAS-FIRED WATER BOILER — Boiler Manual
38
Operation — sequence (continued)
9a
— The circulator continues to operate.
7.
Lower room thermostat setting to stop call for heat. Thermostat is satisfied — Pilot and main gas valves are
closed — Inducer operates for 15-second postpurge — Circulator is shut off.
8. Boiler is now in the off cycle.
9. Repeat steps 1 through 6 several times to verify operation.
10.
Return the thermostat to normal setting.
11. Set thermostat heat anticipator setting as instructed in Figure 32, page 40.
Figure 30 
STEPS

Call for
Heat?
POWER TSTAT
CIRC
LIMIT PURGE FLAME LWCO
Timing
1. Standby
Waiting for call for heat
NO
2. Call for heat
• Circulator on
YES
3. Limit circuit
Limit controls closed
Rollout TFE contacts closed
YES
4. Inducer
Inducer turns on
YES
5. Pressure circuit
Pressure switch contacts closed
Prepurge for 10 seconds
YES
35
sec
6. Flame proven *
Gas valve open
Ignitor remains on
Boiler producing heat
YES
15
sec
7. Limit cycle
Limit circuit open
Gas valve closed
YES
8. Flame outage *
• Flame out
• Boiler recycles
YES
9. Thermostat satisfied
• Circulator off
NO
15
sec
10. Circulator exercise routine
Circulator turns on for 30 seconds if
boiler not operated for 30 days
NO
30
sec
11. LWCO circuit
LWCO circuit open
YES/NO
= ON
= OFF
 






• 
