CGi Manual

Part Number 550-142-302/0520
CGi
SERIES 4 — GAS-FIRED WATER BOILER — Boiler Manual
55
Troubleshooting — control module lights (cont.)
11c
CHART 3 –– PURGE & POWER light flashing
–– Usually indicates pressure switch stuck closed or failed to make within 5 minutes –– 120
Electrical shock hazardTURN OFF POWER

Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
Thermostat should call for heat and appropriate zone valves open.
Does inducer motor operate?
No Yes
• Replace
control module.
• Retest.
Check air pressure switch
per manual Section 11b.
Replace if necessary.
• Retest.
Clear passages and recycle boiler.
Recheck boiler operation.
Try reseating plug in
module receptacle and
restart.
If inducer still does not
work, replace inducer
assembly.
• Retest.
Boiler should be in
normal operating
sequence.
Observe operation until
thermostat is satisfied
and inducer has
completed its post-purge
cycle.
• Remove INDUCER plug (Figure 38, Item 6, page 52) from
plug receptacle of control module.
Place voltmeter leads across the 120 VAC N and 120 VAC
H pins of the INDUCER receptacle (middle and bottom
pins).
Does the voltmeter indicate 120 VAC?
No Yes
Remove one of the wires connected to the pressure
switch.
Check continuity across the switch terminals.

No Yes
Wait 5 minutes.
Is PURGE
No Yes
Wait 45 seconds.
Does Inducer motor operate?
No Yes
Are vent or combustion air
passages blocked?
No Yes