SERIES 4 — GAS-FIRED WATER BOILER — Boiler Manual
56
Troubleshooting — control module lights (cont.)
11c
CHART 4 –– FLAME & POWER light flashing
$$"%&!!'#!$$120
Electrical shock hazardTURN OFF POWER

• 
TURN OFF POWER
to boiler at service
switch or breaker.
Open main manual gas
valve.
Turn on power
to boiler
at service switch or
breaker.
Restart boiler per operating
instructions.
• Perform start-up
procedures in boiler
manual to verify proper
operation.
Boiler may now be
operating
normally.
• Perform start-up
procedures in
boiler manual to
verify proper
operation.
Replace control module.
• Retest.
Are manual main shutoff valve and gas valve open?
No Yes
Replace gas valve.
• Retest boiler.
Are FLAME & POWER
No Yes
• Replace
control
module.
• Retest.
Boiler should now
operate normally.
• Original flashing
FLAME light
caused by gas
valve not
operating properly.
• See normal
sequence of
operation,
Figure 30,
page 38.
Turn off power to the boiler at service switch or
breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9c).
Look through the pilot inspection port to see if the pilot
is burning during the prepurge period (first 30 seconds
of operation).
Is pilot burning during prepurge period?
No Yes
• Replace
control
module.
• Retest.
Leave main manual gas valve closed.
Turn off power to boiler at service switch or breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9c).
Do FLAME and POWER
No Yes
Allow boiler to continue cycling.
Are FLAME & POWER
No Yes