SERIES 4 — GAS-FIRED WATER BOILER — Boiler Manual
58
Troubleshooting — control module lights (cont.)
11c
CHART 6 –– FLAME light flashing and Power light on steady
Also –– Troubleshooting failure to establish main flame.
Electrical shock hazardTURN OFF POWER

Is pilot flame visible through inspection port ?
No Yes
Are main manual shutoff valve and gas valve open?
No Yes
• 
to
boiler at service switch or
breaker.
Remove burner shield (see
Figure 40, item 4, page 64
for location.
Contact gas supplier to cor-
rect
pressure or gas supply.
Check the voltage
across terminals PV and
C of the gas valve.
Is 24VAC present there?
Yes No
Make sure ground wire
terminal is securely
fastened to control module
mounting screw.
Verify inlet gas pressure at gas valve:
Natural gas – 5.0” w.c. min/14.0” w.c. max
Propane – 11.0” w.c. min/14.0” w.c. max

No Yes
Check the voltage
across terminals of MV
and C
of the gas valve.
Is 24VAC present there?
No Yes
If the wiring from the
control module to gas
valve is intact, replace the
control module.
• Retest.
Verify inlet gas pressure at gas
valve:
Natural gas – 5.0” w.c. min/14.0”
w.c. max
Propane – 11.0” w.c. min/14.0”
w.c. max
Is gas present at gas valve inlet and

Yes No
Boiler should be in
normal operating
sequence.
• Observe operation
until thermostat is
satisfied and blower
has completed its
post-purge cycle.
Verify pilot gas line is not
kinked, obstructed or
damaged and is correctly
attached to pilot and gas
valve.
Verify pilot ignition electrode,
electrode ceramic and spark
lead wire from control are in
good condition. Spark gap
should be approximately 1/8”.
Correct any above problems,
replacing pilot if burner or
wiring is damaged.
Reinstall burner shield to
operate boiler for retest after
any changes or corrections.
If none of the above corrects
problems, then replace the
control module and retest.
• 
to boiler at service switch or
breaker.
Remove burner shield (see
Figure 40, item 4, page 64
for location.
If none of the previous steps
(including replacing pilot)
corrects problem, then replace
the control module, reinstall
burner shield and retest.
If the wiring from the
control module to gas
valve is intact, replace the
control module and retest.
• 

to boiler at service switch or breaker.
Open main manual shutoff valve and boiler gas valve (per
Operating instructions in this manual). Wait at least 45 seconds.
Turn on power at service switch or breaker. Allow boiler to
cycle .
Does FLAME
No Yes
• 
to boiler at service switch or breaker.
Check flame signal – Detach sense lead from ignition control
(Figure 38, Item 8, page 52)
.
• Connect negative lead of MICROAMMETER to control
sense terminal
(Figure 38, Item 8, page 52)
. Connect
positive lead of MICROAMMETER to sense wire.
• DISCONNECT red wire connected to terminal MV of the gas
valve.
Turn on power to boiler and allow to cycle. As soon as pilot
is burning, the MICROAMMETER should read at least 1.0
microamp.

No Yes
Verify pilot burner is securely
attached to pilot bracket, brack-
et is securely attached to cross
tie, and there is no corrosion on
the parts which would affect the
ground path for flame sense.
Verify that pilot flame rod, flame
rod ceramic and lead wire from
control module to flame rod are
in good condition.
Correct any above problems,
replacing pilot if burner or wir-
ing is damaged.