CGi Manual

Part Number 550-142-302/0520
CGi
SERIES 4 — GAS-FIRED WATER BOILER — Boiler Manual
59
Troubleshooting — control module lights (cont.)
11c
CHART 7 –– Troubleshooting LWCO and POWER light Solid
and/or “LCO” shown on display
Electrical shock hazardTURN OFF POWER

System is losing water.
Repair leak and retest.
Is boiler pressurized?
Ye s N o
System was low on water.
Check system fill piping for
leaks or damage.
Pressurize boiler to system design pressure.
Are lights still solid?
No Yes
Check system for leaks.
Is system leaking or not
maintaining pressure?
No Yes
LWCO sensor is bad or fouled.
Clean LWCO sensor
Retest.
Are lights still solid?
No Yes
Sensor is bad. Replace sensor.
• Retest.
Sensor was fouled.
Check water quality and
maintenance schedule.