Installation Guide

Part number 550-100-066/0608
g a s -f i r e d w at e r b o i l e r Boiler Manual
46
Vertical vent/air termination: Separate pipes
Allowable vent/air pipe materials
Use only the materials listed in 1. Figure 32, page 31.
Purchase bird screens for vent and air terminations separately. See 2.
the parts list at the end of this manual.
Maximum piping length
Locate the terminations such that the total air piping and vent pip-1.
ing from the boiler to the termination will not exceed the maximum
length given in Figure 62.
Maximum lengths listed in 2. Figure 62 allow for 1 elbow. Additional
elbows required a reduction in maximum length as explained in
the table notes.
Connecting from termination to boiler
Install the termination penetrations as instructed in the follow-1.
ing. Then proceed to page 48 to complete the piping between the
termination and the boiler.
Determine location
Locate the vent/air terminations using the following guidelines:1.
The air piping must terminate in a down-turned 180-degree return 2.
bend as shown in Figure 63. Locate the air inlet pipe no further
than 2 feet from the center of the vent pipe. This placement avoids
recirculation of ue products into the combustion air stream.
The vent piping must terminate in an up-turned coupling as shown 3.
in Figure 63. The top of the coupling must be at least 1 foot above
the air intake. The air inlet pipe and vent pipe can be located in
any desired position on the roof, but must always be no further
than 2 feet apart and with the vent termination at least 1 foot
above the air intake.
You must consider the surroundings when terminating the vent 4.
and air:
Position the vent termination where vapors will not damage a.
nearby shrubs, plants or air conditioning equipment or be
objectionable.
The ue products will form a noticeable plume as they con-b.
dense in cold air. Avoid areas where the plume could obstruct
window views.
Prevailing winds could cause freezing of condensate and water/c.
ice buildup where ue products impinge on building surfaces
or plants.
Avoid possibility of accidental contact of ue products with d.
people or pets.
Do not locate the terminations where wind eddies could affect e.
performance or cause recirculation, such as inside building
corners, near adjacent buildings or surfaces, window wells,
stairwells, alcoves, courtyards or other recessed areas.
Do not terminate above any door or window. Condensate can f.
freeze, causing ice formations.
Locate or guard vent to prevent condensate damage to exterior g.
finishes.










Feet Elbows Feet Elbows Feet Elbows
80 30 1 100 1
Not
allowed
105 30 1 100 1
155 Not allowed 100 1
230 Not allowed 30 1 100 1
310 Not allowed Not allowed 100 1
* Install reducers as necessary where connecting to the boiler
vent and air connections.
For piping using more than 1 elbow, reduce maximum allow-
able length:
• 7 feet for each additional 4-inch elbow (90° or 45°)
• 7 feet for each additional 3-inch long radius elbow
• 16 feet for each 3-inch short radius elbow
• 7 feet for each 3-inch 45-degree elbow.
• 14 feet for the air termination return bend
 Vertical termination — separate pipes