Installation Guide

Part number 550-100-066/0608
g a s -f i r e d w at e r b o i l e r Boiler Manual
54
ondary heat source when another heat source, such
as a heat pump or another boiler is available.


The U-Control provides the exibility for control •
of multiple Ultra boilers.
You will need to program the boilers’ U-Controls •
based on the interconnection method you choose.

The boiler is shipped with an outdoor sensor, a •
system supply sensor and a system return sensor.
The system supply sensor will be required for most
space heating applications. The system return sensor
must also be installed when using the system supply
sensor. Use of the outdoor sensor is optional.
Line voltage power input
Provide and install a fused disconnect or service switch 1.
(15-ampere rated recommended) as required by ap-
plicable codes.
Connect minimum 15-ampere, 120 VAC power wiring 2.
to Ultra boiler line voltage terminal strip as shown in
Figure 78, page 55 and above.
Wiring circulators
The U-Control provides for connection of up to three 1.
circulators, one of which must be the boiler circulator.
In addition, you can connect a system circulator and a
DHW circulator, for examples.

    
. For
circulators with higher amp ratings, you must
install a circulator relay or starter to provide
line voltage to the circulator. For circulators
rated over 2.2 amps, connect only the circula-
tor relay or starter coil to the Ultra circulator
terminals.
Wiring — general
The U-Control provides plug-in, color-coded, non-interchangeable 1.
terminal strips for all field wiring. See the schematic diagram (Fig-
ure 78, page 55) & ladder diagram (Figure 79, page 56).
The U-Control provides programmable exibility in system op-2.
eration, allowing control of heat supply for up to three different
heating systems. Read this manual thoroughly before connecting
the wiring to ensure trouble-free start-up and operation.
Wiring — overview
You will need to make the following connections, some of which
depend on your system and how the U-Control will be programmed.
(See this and following pages for more information.)



Two different circuits are available The U-Control will •
require manual reset for one of these circuits. The U-Control
will automatically reset after limit operation and re-closure for
limits in the other circuit.

The U-Control can regulate the boiler for up to three different •
heating systems.

The U-Control will operate and modulate the boiler based •
on a 0–10 VDC control signal from a remote controller, when
desired.


The U-Control allows the boiler to act as the primary or sec-•
Field wiring

   For your
safety, turn off electrical power supply at service
entrance panel before making any electrical connec-
tions to avoid possible electric shock hazard. Failure
to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1. If original wiring as
supplied with boiler must be replaced, use only type
105 °C wire or equivalent. Boiler must be electrically
grounded as required by National Electrical Code
ANSI/NFPA 70 – latest edition.
Installation must comply with:
1. National Electrical Code and any other national, state, provincial or
local codes or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local
codes.
