Install Instructions

Part number ULT-E022-A_0513
Installation and Instruction for
Condensate Neutralizer Kits
For use with Weil-McLain Condensate Neutralizer Kit
Part Numbers 383-500-631, 383-600-076 & 383-600-287
Hazard definitions
The following defined terms are used throughout these instructions to bring attention to the presence of hazards of
various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related
to personal injury or property damage.
To the installer:
These instructions must only be used by a qualified installer/service technician. Read these instructions
completely before beginning the installation. Failure to follow all instructions can cause severe personal
injury, death or substantial property damage.
Do NOT exhaust flue gases through the condensate tube, it is not rated for boiler or furnace flue gases.
Operating the condensate tube as an exhaust vent can cause injury or death from carbon monoxide.
Application: Condensing boilers and furnaces.
Kit Contents: P/N 383-500-631, 383-600-076 & 383-600-287
(1) Condensate Neutralizer Tube (383-500-631 14” 525MBH, 383-600-076 19” 1000MBH)
(383-600-287 24” 3000MBH)
(2) Barb Fitting 1/2 NPT x 1/2” O.D. (383-500-631 & 383-600-076)
(2) Barb Fitting 3/4 NPT x 3/4” O.D. (383-600-287)
(1) Plug 1/2 NPT
(1) Installation Instructions for Condensate Neutralizer Kit (ULT-E022-A)
Instructions:
Step 1 Turn off electrical power to the boiler or furnace.
Step 2 Turn off main manual gas shutoff to the boiler or furnace.
Step 3 If you are using this kit to replace an existing condensate drain line, detach the existing condensate line from the
boiler or furnace connection.
Step 4 Connect plastic tubes or PVC piping from boiler or furnace condensate trap outlet to either one of the two
neutralizer side inlets. Insert the 1/2 NPT Plug in the remaining neutralizer inlet. Connect the neutralizer end
outlet to floor drain or condensate pump, making sure the drain line runs level or continuously downhill. Drain
line must not be higher than the tee at jacket.
to condensate pump
or oor drain
Must be at
12 O’clock position
Condensate line
(Field Supplied)
Condensate trap tee
Condensate line
(Field Supplied)