Install Instructions (Venting)

Part number 550-100-103/1110
A–27
GAS-FIRED WATER BOILERManual addendum — Venting
Boiler vent and air connectionsFigure 32
Inserting/securing vent or air pipe
into boiler connectors
AL294C vent pipe — If using AL294C stainless
vent pipe, you must install a PVC-to-vent pipe
adapter at the boiler vent connection (and at
the termination if using the Weil-McLain plate
or the concentric termination). Use only the
adapter made by the vent pipe manufacturer.
PVC/ABS pipe — Clean and chamfer insertion end of 1.
pipe. Deburr inside of insertion end. Clean and deburr
inside and outside of other end of pipe.
The pipe end must be smooth and chamfered
to prevent possible damage to sealing gasket
in vent or air pipe adapter. Failure to comply
could result in leakage, causing possible severe
personal injury or death.
Inspect vent or air adapter (above) — verify no obstruc-2.
tions or foreign objects inside.
Loosen clamp screw.3.
Measure 3½ inches from end of pipe and make a mark 4.
with felt-tip pen.
Loosen adapter clamp screw.5.
Apply small amount of silicon grease to end of pipe to 6.
ease insertion.
Insert pipe into adapter.7.
Slide pipe down until the 3½-inch mark is reached.8.
Do not apply excessive force or bend the adapter
or flue/air pipe when inserting. The adapter or
seal could be damaged.
Secure vent or air pipe by tightening the adapter clamp 9.
securely. Do not overtighten. The seal is accomplished
with the internal gasket. The clamp is only to hold the
pipe in place.
Air inlet opening protection: Obtain a bird
screen (sized for air inlet opening) the from
Weil-McLain. Insert the bird screen into the
air inlet opening to prevent foreign objects
from falling into the opening.
Install vent — from boiler to termination (continued)