Ultra Boiler Manual

Part number 550-100-440/0122
125


MAINTENANCE & SPECIFICATIONS
e boiler contains ceramic ber materials. Use care
when handling these materials per instructions on
page109 of this manual. Failure to comply could
result in severe personal injury.
1. Shut down boiler:
a. Follow “To Turn O Gas to Appliance” instructions on
boiler and Lighting instructions.
b. Do not drain boiler unless it will be exposed to freezing
temperatures. If using freeze prevention uid in system,
do not drain.
2. Allow time for boiler to cool to room temperature if it has
been ring.
3. Remove boiler door by removing two (2) screws at lower front.
Li door away from boiler to remove.
4. Follow the applicable procedures under “Accessing & cleaning
heat exchanger:Ultra-80 and Ultra-105 Only” on page126 or
Accessing & cleaning exchanger: Ultra-155, -230, -299 and
-399 Only” on page127.
Clean the cast aluminum heat exchanger when
required — water side
1. In order for the eciency of boilers to increase beyond the
condensing limit, new materials have been introduced for the
heat exchanger, including aluminum.
2. Aluminum has excellent heat transfer characteristics and is
light in weight.
3. ese new materials also require cleaning solutions that dier
from those used in conventional cast iron and steel boilers.
One common cleaning method that CANNOT be
used with systems containing aluminum is a solu-
tion of trisodium phosphate, commonly referred to
a s T S P.”
The reason that trisodium phosphate cannot be
used is that the cleaning solution has a very high pH
level — while removing the scale in the system, it
also removes the natural protective oxide layer from
the aluminum. e oxide layer will reform, but if
small amounts of the trisodium phosphate remain
in the system, the chemical will continue to remove
the protective oxide layer, leading to reduced heat
exchanger life.
4. Use ONLY the cleaning product available from WM Technolo-
gies, Sentinel X400. See the Repair Parts section at the end of
this manual for ordering information.

1. Oil motor in system requiring regular oiling.
2. See Oiled bearing circulators for motor oiling procedures.

1. e circulator shipped with the Ultra boiler is water-lubri-
cated. No oiling is required.
2. Check other circulators in the system. Oil any circulators
requiring oil, following circulator manufacturer’s instruc-
tions. Over-oiling will damage the circulator.



Electrical shock hazard — Disconnect all elec-
trical power to the boiler before attempting
maintenance procedures. Failure to complete
could result in severe personal injury, death
or substantial property damage.


Reinstall boiler jacket front door aer start-
up or servicing. e boiler front door must
be securely fastened to the boiler to prevent
boiler from drawing air from inside the boiler
room. is is particularly important if the
boiler is located in the same room as other
appliances.
Inspect boiler jacket door gaskets. Gaskets
must be in good condition, with no tears or
gaps. Replace if necessary.
Failure to keep the door securely sealed and
fastened could result in severe personal injury
or death.

Removing and reinstalling components can
change boiler behavior. Aer any mainte-
nance procedure, you must prove the boiler
is operating correctly. To do so, follow the
complete procedure for boiler and system
start-up, beginning on page35. Failure to
comply could result in severe personal injury,
death or substantial property damage.

Attention to homeowners and installers
of Ultra Series 4 boilers– see page126
for the latest cleaning information for
our newly coated heat exchangers.