Ultra Boiler Manual
Part number 550-100-440/0122
95
ADVANCED INSTALLATION
Continued after page 98
(see Figure 111, page 96 & Figure 112, page 97) (cont.)
make sure to connect the DHW circulator to termi-
nals1, 4 and7, as below:
4. e factory
default for space heating is designed for
nned-tube baseboard, and set up to activate Circula-
tor2 and Circulator3 on a call for heat. Connect the
boiler circulator to terminals2, 5 and8 and the system
circulator to terminals3, 6 and9 to use these default
settings.
5. Make sure the U-Control is programmed to activate
the system circulator when it is required (during space
heating, for instance).
Use isolating relays if using 3-wire zone valves
to avoid damage and nuisance problems due
to stray voltage.
1. e U-Control allows operation by up to three dierent
heating systems.
2. e factory default conguration is for “heat demand1”
to be DHW and “heat demand2” to be space heating.
For factory default operation:
a. Connect the space heating thermostat to terminal
strip P15, terminals1 and2 to use the default setup.
b. Connect the DHW tank temperature control across
terminal strip P11, terminals4 and5 to use the
default setup.
3. Install thermostats on inside walls away from the inuences of
dras, hot or cold water pipes, lighting xtures, television, sun
rays, or replaces.
4. ermostat anticipator (if applicable):
• If connected directly to the boiler, set anticipator for 0.1amps.
• If connected to relays or other devices, set to match total elec-
trical power requirements of connected devices. See device
manufacturers’ specications and the thermostat instructions
for details.
1. See the NOTICE on this page regarding internal low water protec-
tion provided by the U-Control.
2. When an external low water cut-o is installed, connect as shown
in the U-Control wiring diagrams (Figure111,page96 & Fig-
ure112,page97).
3. When possible, use the Weil-McLain Ultra low water cut-o kit
listed in the back of this manual. It includes a probe-type low water
cut-o and provides a simple harness connection for the wiring.
1. e U-Control and internal sensors in the Ultra boiler provide
both temperature control and low water protection (using
temperature senors), as explained below:
e U-Control module uses temperature sensors to
provide both high limit protection and modulating
temperature control.
e U-Control module also provides
low water
protection
by using a dual sensor to monitor the
temperature of the heat exchanger. [e U-Control
constantly monitors the sensor signals to ensure
they are within 10 °F of one another. If the sensor
dierence exceeds 10 °F, the boiler is shutdown on
automatic reset.] is method is accepted in many
areas as meeting the requirement for a low water
cut-o.
Some codes or jurisdictions may require additional
external controls for high limit and/or low water
cutoff protection. Follow the guidelines in this
manual to install additional controls when required.
Figure 110 Wiring to circulators