Ultra Boiler Manual

Part number 550-100-440/0122
98


(see Figure 111, page 96 & Figure 112, page 97) (cont.)

1. e U-Control allows connection of external limit controls,
both for manual reset and for automatic reset operation of the
U-Control.
2.
Manual reset of the U-Control on limit action — Connect
external limits across P13, terminals1 and2 if the U-Control is
to require manual reset when a limit opens, even if the limit re-
closes. (Remove the factory jumper when using these terminals.)
e U-Control will lockout when a limit in its manual
reset circuit opens. e U-Control activates its alarm
terminals and shuts the boiler down until an operator
manually resets the U-Control (as explained in this
manual). is reset function can be done by a home-
owner or a service technician.
3.
Automatic reset of the U-Control on limit action — Connect
external limits across P13, terminals3 and4 if the U-Control is to
reset automatically when the limit circuit closes aer a limit con-
dition. (Remove the factory jumper when using these terminals.)

1. e U-Control module provides terminals to input a remote
0–10VDC operating signal. is can be provided by a separate
controller if the boiler is congured as Type4 (SHADOW boiler
mode).
2. Connect the 0–10VDC signal positive terminal to P15 termi-
nal6, and the signal common to terminal5.
3. When receiving a remote operating signal, the boiler starts when
the signal exceeds 1.0VDC (and shuts o if the signal drops
below 0.5VDC). e boiler remains at low re until the signal ex-
ceeds 2.0VDC. Between 2.0and 10.0VDC, the boiler ring rate
increases with the signal value, reaching full input at 10.0VDC.
4. e U-Control continues to monitor boiler temperatures, based
on the values set up under Priority1 operation. See the following
section for details.

1. e U-Control module can be set up to activate another heat
source using its additional heat demand dry contracts (P16,
terminals6 and7).
2. Connect these terminals to call for heat from the other heat
source. (See the following section to program the boiler to ac-
tivate the other source, either as the primary or secondary heat
source.)
(low voltage ONLY)
1. e U-Controls alarm dry contact (P16, terminals4 and5) closes
when the boiler enters lockout.
2. Connect these terminals for remote alarm notication.

1. e U-Control can be programmed to sequence multiple boilers
or operate/modulate in tandem from a 0–10VDC source gener-
ated by the lead boiler or from a remote controller.
2. See ADDITIONAL HEAT DEMAND” on page99 for recom-
mended wiring.
Outdoor temperature sensor
1. e U-Control provides programmable options when
using an outdoor temperature sensor. is sensor is
supplied with the boiler, and can be used if desired (not
required). See the following section for outdoor tem-
perature options.
The outdoor sensor must be

Energy Act statement on page 137.
2. Mount the outdoor sensor on an exterior wall, shielded
from direct sunlight or ow of heat or cooling from
other sources.
3. Connect the sensor leads to P10, terminals1 and2, as
shown in the wiring diagrams. ermostat wire can be
used to connect the sensor.

temperature sensors
(see Figure 4, page 11 for placement of sensors)
1. e boiler is also shipped with two strap-on temperature
sensors, intended for system supply and return.
2. ese sensors can be attached to piping up to 3-inch
diameter.
3. ermostat wire can be used to connect these sensors.
4. e system supply temperature sensor allows the U-Con-
trol to regulate temperature in the system main piping.
5. Locate the supply sensor at least six pipe diameters, but
no further than 3 feet, downstream from the boiler con-
nection to the main to ensure adequate mixing.
6. e system return sensor allows the U-Control to moni-
tor and display system return temperature.
7. For multiple boiler applications, install a system supply
temperature sensor and system return sensor wired to
the LEAD boiler.
8. e U-Control also compares the system return tem-
perature with the system supply temperature. Should the
return temperature ever exceed the supply temperature,
the U-Control knows there is likely a sensor failure and
will report this problem on the display.