Table 10 GOLD WGO oil-red water boiler ratings
®
DOE
AHRI Certied Ratings
Boiler
Model
(9)
Burner Input
Heating
Capacity
Seasonal
Efciency
Net
Rating
(water)
Boiler
Water
Content
Flue
Outlet
Diameter
Minimum
Chimney
Draft
Loss
Thru
boiler
GPH
(3)
MBH
(3)
MBH
(2) (4)
AFUE
%
MBH
(2) (5)
Gallons Inches
(7)
Rect
In
Round
In
Height
Ft
In W.C.
(8)
*WGO-2 0.70 98 86 86.4 75 11.0 7 8 x 8 6 15 0.010
*WGO-3R 0.80 112 98 86.2 85
14.9 7 8 x 8 6 15
0.020
*WGO-3 0.95 133 115 85.3 100 0.020
*WGO-4R 1.00 140 122 86.2 106
13.4 7 8 x 8 6 15
0.010
*WGO-4 1.20 168 145 85.0 126 0.010
*WGO-5R 1.20 168 147 86.1 128
15.9 7 8 x 8 7 15
0.015
*WGO-5 1.45 203 175 85.0 152 0.015
*WGO-6R 1.40 196 171 86.1 149
18.4 7 8 x 8 7 15
0.015
*WGO-6 1.75 245 212 85.0 184 0.015
*WGO-7R 1.60 224 196 86.0 170
20.8 7 8 x 8 8 15
0.015
*WGO-7 2.00 280 242 85.0 210 0.015
**WGO-8 2.30 322 266 (6) - 231 23.3
7 8 x 12 8 20
0.025
**WGO-9 2.55 357 295 (6) - 257 25.8 0.030
* Substitute “P” for completely assembled packaged boiler without burner (WGO-3 through WGO-6 only).
Substitute “A” for boiler only for use with approved burners as listed with AHRI.
** Available only as an “A” unit.
(1) WGO boiler designed with convertible vertical and horizontal ue outlet.
(2) MBH refers to thousands of Btu per hour.
(3) Based on 140,000 Btu/gal.
(4) Based on standard test procedures prescribed by the United States Department of Energy at combustion condition of 13.5% CO
2
and -0.02” W.C. dra overre.
(5) Net AHRI ratings are based on net installed radiation of sucient quantity for the requirements of the building and nothing
need be added for normal piping and pick-up. Water ratings are based on a piping and pick-up allowance of 1.15. An additional
allowance should be made for unusual piping and pick-up loads.
(6) AHRI gross output.
(7) See page 12 for minimum breeching diameter.
(8) Listed dra losses are for factory-shipped settings.
(9) Boiler model suxes: “R” designates a reduced input version. NOTE: A burner nozzle change is required — refer to the burner
instructions or boiler’s rating label for correct selection.
Ratings