WTGO Boiler Manual

Part number 550-141-825/1211
8
GOLD
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Before installing boiler
Homeowner STOP! The procedures and information on this and following pages are intended only for a quali-
fied service technician who has the necessary equipment to inspect and adjust boiler and burner. A homeowner
should never attempt these procedures. The service technician must also read pages 1 through 7 before proceeding.
Top View
Walls
Wall
Figure 2 Recommended service clearances
Left side
A Provide 6" minimum clearance for service, provide 12"
minimum clearance for burner door swing.
B Minimum clearance from vent pipe to combustible mate-
rial: 6" for type “L double-wall vent, 9" for single-wall
vent.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors
can result in severe personal injury, death or substantial property damage.
Installations must comply with
• United States
• State and local plumbing, heating and electrical codes.
• National codes where applicable.
• Canada
• Canadian Standards Association, CSA B139, Installation Code for
Oil-Burning Equipment.
• CSA C22.1 Canadian Electrical Code Part One.
• Applicable local or provincial codes.
Before selecting boiler location
• Check for nearby connections to:
• System water piping.
• Chimney. See page 16. Boiler can be top or back vented.
• Combustion and ventilation air supply. See page 9.
• Oil supply. See page 28 for oil line routing.
• Electrical power.
• Check area around boiler. Remove any combustible materials, gasoline
and other flammable liquids.
Provide clearances around boiler
(see Figure 2)
Jacket cap must be in place on boiler to
avoid requiring an 9" minimum clearance
from back or top of boiler to combustible
material.
• MINIMUM clearances from vent pipe to combus-
tible material:
• 6 inches Type “L double-wall vent*
• 9 inches Single-wall vent
Flue pipe clearances must take precedence
over jacket clearances.
• Recommended SERVICE clearances:
• 24 inches Front and top
• 6 inches Left side, back and right side
• 12 inches Right side for burner door swing
radius
• Special close clearances (alcove, closet, under counters,
etc.) — see Appendix, page 34.