Specifications

Part number 550-100-090/0809
123
g a s -f i r e d w a t e r b o i l e r Boiler Manual
MAINTENANCE & SPECIFICATIONS
Ratings — multiple Ultra boilers (continued)
Figure 127 Engineering data (see Figure 128 for notes)
Boiler
Model
Ultra –
Shipping
weight
Operating
weight
Water
content
Water flow rate
per boiler
Vent/air pipe
size —
Provide a
separate vent
for each boiler
Electrical
service
required
Pounds
per boiler
Pounds
per boiler
Gallons
per boiler
GPM
@ 20°F rise
GPM
@ 40°F rise
Amps
per boiler
Note 4 Note 5 Note 6
80
199 139 0.7 7.1 3.6 2” or 3” 15.0
105
207 145 0.8 9.4 4.7 2” or 3” 15.0
155
234 181 1.2 13.9 7.0 3” 15.0
230
246 192 1.6 20.7 10.4 3” or 4” 15.0
299
297 229 2.1 27.9 14.0 4” 15.0
399
297 229 2.1 36.5 18.2 4” 15.0
Figure 128 Notes for Figure 126 and Figure 127-
1
Based on standard test procedures outlined by DOE for individual boilers.
2
Net I=B=R ratings are based on piping and pickup allowance of 1.15.
Consult Weil-McLain Technical Services for other allowances.
3
Foundation sizes in Figure 126 provide 6 inches between boilers and 2 inches from boiler to edge of foundation.
Smaller foundations are possible with reduced service clearances.
See page 54 for details.
For side-to-side installations, see • Figure 56, page 54.
For back-to-back installations, see • Figure 57, page 54.
4
Operating weight is the total weight of the boiler, including water.
5
Ultra-80 and -105 vent/air pipes can be either 2” or 3” pipe. Vent/air pipe length limits for 2” piping are not as long as for 3” piping.
Ultra-230 vent/air pipes can be either 3” or 4” pipe. Vent/air pipe length limits for 3” piping are not as long as for 4” piping.
All Ultra installations require a separate vent pipe and termination for each boiler.
Vent piping cannot be manifolded. Install and
terminate vents as described in vent/air installation instructions in this manual.
Combustion air piping can be individually piped or manifolded. See Figure 59, page 55, for manifolded air piping.
6
Total amp requirement includes up to three circulators, not exceeding 2.2 amps per circulator.