g a s -f i r e d w a t e r b o i l e r Boiler Manual
MAINTENANCE & SPECIFICATIONS
Annual startup (continued)
If flame signal still remains low, inspect the vent and air 4.
piping. Then inspect the heat exchanger, following the pro-
cedures given in this manual for removal and reinstallation
of the head exchanger cover plate and other boiler compo-
nents. Clean the exchanger as described in this manual if
necessary.
Check blower speeds
For installations at altitudes above 5,500 feet, make sure the 1.
control is set up for high altitude in the boiler setup menu.
The U-Control module automatically adjusts low fire and
ignition rates to compensate for high altitude conditions.
For installations below 5,500 feet, high altitude should NOT 2.
be enabled.
Use the U-Control display to navigate to Manual test mode 3.
(see Figure 102, page 86).
Set the firing rate to MINIMUM (low fire).4.
Write down the blower RPM value shown and compare to 5.
the value in Figure 108. The value should no less than the
“Minimum setting” and no higher than the Ignition “Fac-
tory setting” listed. Low fire rate (and corresponding blower
speed) is adjusted in the boiler setup menu.
Set the firing rate to MEDIUM (ignition rate).6.
Write down the blower RPM value. It should be within 200 7.
RPM of the value listed in Figure 108.
Set the firing rate to MAXIMUM (high fire).8.
Write down the blower RPM value. It should be within 200 9.
RPM of the value given in Figure 108.
If any of the values are outside the ranges listed in the previous 10.
steps, contact the factory for technical assistance.
Check flue gas temperature
Set the boiler to high fire. Then adjust the U-Control mod-1.
ule display to view flue gas temperature and boiler return
temperature.
The flue gas temperature should be no more than 54 °F higher 2.
than the boiler return temperature.
If the flue temperature is higher than this, shut down the 3.
boiler, allow to cool, and follow the procedure starting on
page 109 to clean the heat exchanger.
Firing rates and corresponding blower speeds (low fire, ignition, and high fire) — for altitudes up to 5,500 feetFigure 108
ULTRA Model 80 105 155 230 299 399
% RPM Btu/Hr % RPM Btu/Hr % RPM Btu/Hr % RPM Btu/Hr % RPM Btu/Hr % RPM Btu/Hr
Low fire
Minimum setting
20 1,300 16,000 20 1,300 21,000 20 1,300 31,000 20 1,300 46,000 20 1,400 62,000 20 1,520 79,800
Factory setting
33 1,983 26,400 33 1,983 34,650 33 1,983 51,150 33 1,983 75,900 33 2,156 102,300 20 1,520 79,800
High altitude
33 1,983 26,400 33 1,983 34,650 33 1,983 51,150 33 1,983 75,900 30 1,981 93,000 28 2,002 111,720
Ignition (“Medium” setting in manual test mode)
Factory setting 47 2,300 37,600 47 2,300 49,350 47 2,300 72,850 47 2,300 108,100 36 2,330 111,600 33 2,303 131,670
High altitude 62 3,500 49,600 62 3,500 65,100 62 3,500 96,100 62 3,500 142,600 51 3,202 158,100 40 2,725 159,600
High fire (adjust if desired to match maximum system load — High fire % rate = Max heat load / Boiler output)
Factory setting
94 5,200 75,200 94 5,200 98,700 94 5,200 145,700 94 5,200 216,200 96 5,818 297,600 96 6,099 383,040
Maximum setting
100 5,500 80,000 100 5,500 105,000 100 5,500 155,000 100 5,500 230,000 100 6,050 299,000 100 6,340 399,000