Instruction manual
Part number 550-100-116/0714
26
SlimFit
™
COMMERCIAL CONDENSING GAS-FIRED WATER BOILER
— Boiler Manual
&IGURE Piping layout — typical piping for multiple SlimFit boilers, with DHW storage heater (or heaters) direct-piped to
one of the boilers
SF3158a
1
2
3
4
5
6
7
8
9
13
17
18
19
25
30
2
2
2
2
36
4
5
1
2
3
17
25
2
1
2
3
17
25
2
37
2
21
27
Drain
valve
2
30
Multiple boiler water piping (continued)
Legend — Figure 24
1 Check valve (each boiler)
2 Isolation valves
3 Strainer (recommended on return line to each
boiler)
4 Multiple boiler manifold (supply) layout and
size per Figure12, page15
5 Multiple boiler manifold (return) layout and size
per Figure12, page15
6 Primary pump
7 Expansion tank (diaphragm type shown)
8 System air eliminator
9 System automatic air vent
13 Cold water supply (requires items 10, 11 and 12 as
shown in Figure21, page23)
17 Boiler pump (each boiler)
18 System supply
19 System return
20 Boiler relief valve and discharge piping (not shown)
install per page14 and all applicable codes
21 Indirect-red storage water heaters (Weil-McLain
AQUA shown). See water heater manual for DHW
piping.
25 External drain/blowdown valve, when used, ¾”
NPT or larger
27 Flow/check valve in DHW piping
30 Strap system supply sensor to the system pipe
as shown. Place sensor at least 6 pipe diameters,
but no more than 10 pipe diameters, from boiler
supply connection to the system pipe.
36 Secondary connection to boiler manifolds space
no greater than 8 pipe diameters apart
37 DHW pump
Set the Sola control so the boiler pumps, item 17, operate
on any call for heat, whether heating system or DHW.
Oset the DHW boiler-side supply and return manifolds
as shown so the total run of pipe and ings to each of
the water heaters is approximately equal.
DHW tanks piped using this arrangement need to be sized for
the required load, with a DHW pump selected to provide a ow
rate through the boiler and tank that is within the allowable ow
rate range listed in Figure13, page15 of this manual.
r Use 3” or larger piping for all
connections between boilers and
manifolds.
r Follow all sizing guidelines on
page15. Pumps must provide
ow rates required.
r Use recognized engineering
design practices throughout.