Installation manual

Northern Health
Lakes District Hospital and Health Care Centre
Burns Lake, B.C
Section 11 40 03
FOODSERVICE - EQUIPMENT
ITEMIZED SPECIFCATIONS
Page 2 of 18
Epoxy coated finish
4 posts, 74P, per unit or common posts permitted where units are end to
end, with floor plates
5 shelves per unit
Note: Verify sizes with room conditions, prior to ordering
ITEM 4
WALK-IN ASSEMBLY 1 REQUIRED
Manufacturer: Norbec
Model: Prefabricated Modular Walk-ins *L046
Approved
Alternate:
Kysor equivalent
MasterBilt equivalent
Unit: Cooler Cooler
Size: Approx. 2351 x 3072 x 2590 high
above finished floor
Approx. 3450 x 3072 x 2590 high
above finished floor
Door: 1 required standard
1 required standard
Components: 1 required door light fixture
2 required fluorescent light
fixtures
1 required door light fixture
1 required fluorescent light fixtures
Construction: Standard as specified
Full box unit; walls, ceiling and floors.
Floor – Type A floor (integral insulated floor) as specified with locking
screed; (floor to withstand concrete leveling topping and floor finish)
4”/100 mm minimum foamed in place urethane walls, ceilings and floors
Interior and exposed exterior with white baked enamel finish, embossed
finish texture
Unexposed exterior with galvanized finish
Exterior to have 250mm/10” wide stainless steel flush wall impact plate on
exposed traffic areas
Doors: Standard 36” x 78” (915 x 1981 mm) flush mounted doors, hinged as shown
on the plan with,
Magnetic gasket, positive latching, self-closing, safety release hardware,
provision for padlock, cam lift hinges spring assisted and door snubber each
door
Threshold anti-condensate heater
Stainless steel kickplate on interior and exterior of each door, 915 mm/36”
high
Door section to have incandescent type vapour-proof light, remote exterior
mounted switch and conduit between switch and outlet box – wiring to be
pre-wired and concealed, with automatic lighting control
Components: Walk-in flush mounted integral audio-visual digital alarms with mute and
reset – Intelligence module, with automatic lighting control
Internal panic button
Manufacturer’s standard 1220mm/48” low temperature fluorescent light
fixtures with bulbs or equivalent
Closure panels to ceiling, if required – removable/vented for accessibility as
required, finished ceiling, colour to match walk-in finish, ceiling height 2745
Trim strips to wall - colour to match walk-in finish
Services: Refer to Services Schedule
Note: FEC to verify clearances of finished ceiling height, finished floor to
underside of ceiling work above to ensure proper installation access, fit, and
operation of systems