Installation manual

Northern Health
Lakes District Hospital and Health Care Centre
Burns Lake, B.C
Section 11 40 03
FOODSERVICE - EQUIPMENT
ITEMIZED SPECIFCATIONS
Page 3 of 18
FEC to verify site access for panels
FEC to verify site condition for finished ceiling and ceiling system
ITEM 5
REFRIGERATION SYSTEM - COOLER 1 REQUIRED
Manufacturer: Tecumseh/Russell or equivalent
Model: Manufacturers standard as specified *L046
Accessories: Include all components as required and noted under applicable section of
Foodservice Equipment Products with
Water-cooled condensers as specified, sized for walk-ins and use, top
mounted, extended 5 year warrantee, interior location; closed loop, provide
3way valve
Design operating temperature 2
o
C (35
o
F) +/-
Unit coolers sized for walk-in and use and sized to balance with the
condensing unit
Evaporator to have drain pan with suitable drainpipe fitting, air defrost,
extended 5 year warrantee
Installation to include all piping, fittings, controls and accessories as
required for a complete operational installation
Label all refrigeration lines at unit by system
Confirm location – unit to be mounted on top of box, confirm space and air
circulation prior to installation, coordinate with applicable trade to ensure
adequate air circulation for refrigeration systems– notify the consultant in
writing if location is not suitable
Ensure adequate service access to unit provided
Services: Refer to Services Schedule, verify with requirements
Custom Work: Provide stainless steel protective channels around exposed evaporator
piping within walk-in
Note: Electrical disconnect switch to be provided and installed by others (Electrical
Division) per authority having jurisdiction
ITEM 6
REFRIGERATION SYSTEM - FREEZER 1 REQUIRED
Manufacturer: Tecumseh/Russell or equivalent
Model: Manufacturers standard as specified *L046
Accessories: Include all components as required and noted under applicable section of
Foodservice Equipment Products with
Water-cooled condensers as specified, sized for walk-ins and use, top
mounted, extended 5 year warrantee, interior location; closed loop, provide
3way valve
Design operating temperature -24
o
C (-10
o
F)
Unit cooler sized for walk-in and use and sized to balance with the
condensing unit
Evaporator to have drain pan with suitable drainpipe fitting, electric defrost,
extended 5 year warrantee, verify that heat trace and insulation is installed
for the full length of the evaporator drain line – heat trace must be
operational prior to start-up of refrigeration system
Coordinate with Mechanical Contractor for drain line heat coil wrap
Defrost timers
Installation to include all piping, fittings, controls and accessories as
required for a complete operational installation
Label all refrigeration lines at unit by system
Confirm location – unit to be mounted on top of box, confirm space and air