Specifications
INSTALLATION (continued)
FIRE SUPPRESSION SYSTEM INSTALLATION
1. Any REMOTE MANUAL PULL STATION must be installed by an
authorized ANSUL® distributor in accordance with the
AUTHORITY HAVING JURISDICTION.
NOTE: If a REMOTE MANUAL PULL STATION is installed, moving
the unit for servicing will cause the Ansul® system to discharge.
In this case, the unit must only be installed with four xed legs
(i.e. remove rear casters and replace with legs). Additional legs
may be ordered through an Authorized Wells Service Agency. See
page 25.
2. The FIRE SUPPRESSION SYSTEM is comprised of a
pressurized cartridge
& container of liquid
re suppressant, with
associated plumbing and
controls. It utilizes factory
installed FUSIBLE LINKS
for automatic actuation,
and a factory installed
MANUAL PULL STATION
for manual actuation.
Two NOZZLES are used
to disperse the liquid re
suppression media.
3.
When the re suppression
system activates, the
re suppression media
is discharged, both the
cooking appliance and
the
ventilator are de-
energized, and a buzzer
will sound continuously.
The re suppression
media will form an emulsion designed to both smother and cool the
re.
Call your
Authorized Ansul® Distributor immediately for service.
NOTE: See page 28 for the Material Safety Data Sheet for the re
suppression agent.
4.
The MANUAL PULL STATION and any similar REMOTE MANUAL
PULL STATION will activate the re suppression system when the
ring on the pull station is pulled horizontally.
DANGER
FIRE
HAzARD
THE FIRE SUPPRESSION
SYSTEM MUST BE
CHARGED AND CERTIFIED
BY AN AUTHORIZED
ANSUL® DISTRIBUTOR.
NEVER ATTEMPT TO
MODIFY OR BYPASS
THE FIRE SUPPRESSION
SYSTEM. AN
UNCONTROLLED FIRE CAN
CAUSE SERIOUS INJURY,
DEATH AND/OR PROPERTY
LOSS.
IMPORTANT: The FIRE
SUPPRESSION SYSTEM
must be SET-UP and
CHARGED by an authorized
Ansul® distributor before the
ventilator blower will operate.
NOTE: If the re
suppression system is
discharged, a buzzer will
sound continuously and
the cooking appliance will
remain inoperable until the
re suppression system
is serviced. Recharging
and resetting must be
performed by an authorized
Ansul® distributor ONLY.
Charging of the Ansul
Fire Suppression system
must be in accordance
with Ansul® Design,
Installation, Recharge
and Maintenance Manual.
(Ansul® #418087-05)
FIRE SUPPRESSION
AGENT DISPENSING
NOZZLES (2 PLACES)
ALL MODELS SHIP
WITH 2 FACTORY-
INSTALLED
FUSIBLE LINKS
MANUAL PULL
STATION
LOCATION
REAR CASTERS
REPLACED WITH
LEGS WHEN A
REMOTE MANUAL
PULL STATION
IS INSTALLED
REMOVE REAR PANEL
FOR ACCESS TO FIRE
SUPPRESSION SYSTEM
CONTROLS
IL2146
Fig. 6 Fire Suppression System
10