Instruction Manual

I-9.4 Calibration
Press ID to select the input and M to open the calibration page.
Transducer input:
Adjusting the transducer start and end:
Ü
Select Quit Set transducer to start
*
Press MrQuit blinks
Ö
Press IrSet 0% blinks
ä
Wait until the input has settled (min. 6 s)
#
Press Mr0% done is displayed
<
Set transducer to end
>
Press Mr0% done blinks
y
Press I 3x r Set 100% blinks
x
Wait until the input has settled
c
Press Mr100% done is displayed.
Calibration is finished. For exit from calibration press D until nothing is marked and then press M.
Two resistance thermometers:
Calibration of lead resistance effect
Ü
Select Quit .
Short-circuit both thermometers in the connecting head
*
Press MrQuit blinks
Ö
Press IrSet Dif blinks
ä
Wait until the input has settled (min. 6 s)
#
Press MrCal done is displayed
Lead resistance adjustment is finished. Remove both short cir-
cuits. For exit from calibration press D until nothing is marked
and then press M.
I-9.5 Online/Offline
For configuration changing, switch the unit to ‘Offline’ and back to ‘Online’ after alteration.
a
When switching the unit to status off-line, the outputs will remain in the status at switch-over time !!!
+
By switching over to on-line, all data is saved.
+
When terminating the off-line mode by cancellation (Escape config.) the data saved last is loaded back into the wor
-
king memory.
9499-040-82711 Instrument settings in the main menu
Calibration I-35
Transducer
Temp. difference