Installation manual
STARTING/STOPPING
PROCED
GENERATOR
CONTROL
PANEL
AC
CIRCUIT
BREAKER
---~1
Starting
Simply
press
the
START
switch
and
the
generator
will
start.
. A
green
light
will
glow
indicating
the
generator
is
running.
Stopping
To
stop-depress
the
STOP
side
of
the
start
switch,
the
green
light
will
go
out
and
the
generator
is
stopped.
Failure
to
Start
The
start
cycle
will
automatically
terminate
if
the
unit
fails
to
start
after
12-14
seconds
of
cranking.
Wait
20
seconds,
then
repeat
the
start.
If
the
unit
again
fails
to
start,
investigate
the
cause.
Sometimes
after
servicing
the
fuel
system
or
changing
the
fuel
filter,
air
can
accumulate
in
the
fuel
line
or
the
throttle
body
and
prevent
starting.
The
Schrader
valves
on
the
throttle
body
and
the
fuel
cell
are
used
to
remove
trapped
air.
This
air
is
mixed
with
fuel
and
under
high
pressure.
Follow
the
BLEEDING
THE
FUEL
SYSTEM
instructions
in
this
manual.
·
O rw=jWESTERBEKE O
lou~
1
j I
1
o~~~
EJ\IGINE
TEMP
£XH
TEMP
•
START
STOP
D
0
REMOTE
CONTROL
PANEL
7
CONNECTIONS
FIREBOY,
CO
DETECTOR
AND/OR
AUXILIARY
STOP
CONNECTION
REMOTE
START/STOP
PANEL
The
components
on
the
panel
are:
1.
A
three
position
start/stop rocker
switch.
2.
A
green
LED
run
indicator
light
on
the
rocker
switch.
3.
A
four
position
LED
fault
shut
down
display
board.
The
start/stop
rocker
switch
functions
the
same
as
the
start/stop
rocker
switch
on
the
generator's
control
panel
as
previously
explained.
The
start/stop
rocker
switch
indicator light
on
the.
rocker
switch
will
illuminate
when
the
start circuit
is
energized.
It
will
go
dim
as
the
engine
cranks
and
will
brighten
as
the
engine
starts
to
indicate
the
generator
is
running.
The
LED
fault
shut
down
display
board
has
four
separate
LED
lights
to
display
to
the
operator
the
cause
of
the
generators
automatic
shut
down.
The
four
LED
displays
are:
low
oil
pressure,
high
engine
operating
temperature,
high
exhaust
temperature
and
engine
over-speed/under-speed
(flashes).
Should
the
generator
shut
down
from
one
of
these
faults,
the
fault
LED
will
remain
illuminated.
To
reset
the
LED,
the
stop
switch
must
be
momentarily
depressed.
This
remote
panel
is
a
plug-in
accessory
and
is
available
with
a
15'
to
100'
wiring
harness.
CAUTION: Repeated crank cycles without a start can result
in
the engine's exhaust system filling with raw water. This
raw water can enter the engine's cylinders
by
way
of
the
exhaust manifold once the system fills.
If
after three crank
cycles the unit does not start. Drain the system's muffler
and investigate and correct the cause
of
no
start. Engine
damage the result
of
raw water entry
is
not a warrantable
issue. The operator should keep this
in
mind.