Installation manual

AC
VOLTAGE
REGULATOR
(CURRENT
MODELS)
#054596
VOLTAGE
POTENTIOMETER
The output voltage
of
the generator can be adjusted using the
potentiometer with the generator running at its selected speed
(frequency) by turning the adjustment until the desired
voltage
is
obtained.
NOTE:
If
the voltage is set higher than
selected rated voltage, the generator may be damaged.
FREQUENCY
Ajumper
on the regulator
is
connected to two of' the three
pins for either
60 hertz or 50 hertz operation.
NOTE:
This
does not automatically change the engine speed. Engine
speed change
is
performed using the adjustment on the belt
driven mechanical governor.
'f]T.:f·{·::·;··
:··.,
..
·-
50Hz
A~l~
..
,
-
.-JU$.:,;::-:;;~:i:;::/;
......
-
STABILITY
FUSE
3.15A
VOLTAGE
SENSING
AC
VOLTAGE
REGULATOR
#054596
If
at no-load
or
while under load with steady engine speed,
AC output voltage fluctuation
is
experienced. Adjust the
stability potentiometer. This modulates the reaction time
of
the regulator to external inputs, thereby eliminating any
instability in the AC generator load system.
The voltage sensing connections are 0 and
115
when selected
output voltage
is
between 1
OOV
and
140V.
Connect between
0 and
230
when selected output voltage
is
between
200V
and280V.
UNDER
FREQUENCY
The UNDER FREQUENCY potentiometer on the regulator
can not be adjusted in the field. The control
ECU
is
monitoring engine speed and will react to stop the unit
should engine speed fall below a preset level.
The UNDER FREQUENCY circuit in the regulator can be
a cause
of
voltage/light flicker in a new regulator.
If
this
occurs, tum the potentiometer counter clockwise 5-6 turns
to arrest this.
EXCITER
WINDING
Proper polarity in this circuit
must
be maintained. Black to
-
Ex
and
red
to+
Ex. Failure to do so may damage the
regulator.
AUXILIARY
WINDING
Connect the correct color wires to the terminals. Green or
gray to
Aux
L and blue and brown to
Aux
N.
Exciting the generator using an external DC source can be performed
when troubleshooting a generator/AC voltage output issue.
The following procedure should be followed:
1.
The generator should not be operating. Remove
the-
Ex and + Ex.
electrical connections off the regulator.
2. Maintaining polarity. Connect the
+ (plus) from a 9 volt dry cell
battery to the
+.Ex (red I electrical lead coming from the generator
and
the-
(negative) to
the-
Ex (Black electrical lead coming
from the generator.
3. Start the generator and observe the reaction and voltage output
froin the generator and react accordingly.
~
',
~
The trouble.shooting booklet for the BE style generator will help you
~~
""~
· .
1
determine the cause
of
a generator AC voltage output issue by the
~
AC voltage f?und bein? p:oduced by the generator and the reaction g
VOLT
DRY
CELL
of
the generatiOn to excrtatwn.
~
WESTERBEKE i